[PAGE 2] [PAGE 3] Controlled Temperature Chamber Mapping and Monitoring Disclaimer: The ISPE Good Practice Guide on Controlled Temperature Chamber Mapping and Monitoring provides necessary guidance in light of the growing number of products requiring controlled temperature shipping and storage. This Guide is solely created and owned by ISPE. It is not a regulation, standard or regulatory guideline document. ISPE cannot ensure and does not warrant that a system managed in accordance with this Guide will be acceptable to regulatory authorities. Further, this Guide does not replace the need for hiring professional engineers or technicians. Limitation of Liability In no event shall ISPE or any of its affiliates, or the officers, directors, employees, members, or agents of each of them, or the authors, be liable for any damages of any kind, including without limitation any special, incidental, indirect, or consequential damages, whether or not advised of the possibility of such damages, and on any theory of liability whatsoever, arising out of or in connection with the use of this information. All rights reserved. No part of this document may be reproduced or copied in any form or by any means – graphic, electronic, or mechanical, including photocopying, taping, or information storage and retrieval systems – without written permission of ISPE. All trademarks used are acknowledged. ISBN 978-1-936379-86-6 GOOD PRACTICE GUIDE: [PAGE 4] Controlled Temperature Chamber Mapping and Monitoring Preface The ISPE Good Practice Guide on Controlled Temperature Chamber Mapping and Monitoring provides guidance on the definition of the requirements (producing a user requirements document), design, purchasing, commissioning (including temperature mapping), qualification and maintenance of controlled temperature chambers operating under current Good Manufacturing Practices. Types of Controlled Temperature Chambers considered by this guide range from purchased Commercial Off the Shelf items, such as freezers and incubators, walk-in cold rooms and walk-in freezers, to custom built units, such as warehouses. This ISPE Good Practice Guide provides industry good practice for the temperature mapping of controlled temperature chambers, development of test acceptance criteria and a risk based approach to practices for periodic review of system performance. [PAGE 5] Controlled Temperature Chamber Mapping and Monitoring Acknowledgements The Guide was produced by a Task Team led by Nick Haycocks (Amgen Inc.). Core Team The following individuals took lead roles in the preparation of this Guide: Luca Arrighi Amec Foster Wheeler Italy Denise Bender DBender Consulting, LLC USA Mike Bradley Amgen Inc. USA Paul Daniel Vaisala Inc. USA Geoffrey Glauser Health & Human Services USA Paul Harber Modality Solutions, LLC USA Randolph Leinhauser Merck & Co., Inc. USA Elizabeth Martinez Flores, CPIP Terra Farma SA de CV Mexico Matthew McMenamin GlaxoSmithKline USA Derek Moss FUJIFILM Diosynth Biotechnologies USA Mark E. Newton Eli Lilly & Co. USA Brian W. Saxton Compliance Risk Management USA Jean Vezina Salvus Inc. Canada Christopher B. Weaver Elanco USA Mark Zemler FUJIFILM Diosynth Biotechnologies USA Special Thanks ISPE wish to thank Mary White and Dubhaltach Mac Lochlainn of the National Standards Authority of Ireland (NSAI) who provided valuable discussion, advice, and review comments. Particular thanks also go to Peter Diebold (Thermo Fisher Scientific) for his review and comment. Many other individuals reviewed and provided comments during the preparation of this Guide; although they are too numerous to list here, their input and patience in supporting this guide is greatly appreciated. The Team also would like to express their gratitude to Gail Evans and Lynda Goldbach of ISPE for their patience, guidance, and support during the development of this document. Company affiliations are as of the final draft of the Guide. Cover photo: courtesy of Vaisala Inc., www.vaisala.com [PAGE 6] 600 N. Westshore Blvd., Suite 900, Tampa, Florida 33609 USA Tel: +1-813-960-2105, Fax: +1-813-264-2816 www.ISPE.org [PAGE 7] Controlled Temperature Chamber Mapping and Monitoring Table of Contents Introduction.......................................................................................................................7 1.1 Purpose and Objectives...............................................................................................................................7 1.2 Scope...........................................................................................................................................................7 1.3 Benefits.........................................................................................................................................................8 1.4 Regulatory Guidance....................................................................................................................................8 1.5 Key Concepts/Key Terms.............................................................................................................................9 2 Related Standards...........................................................................................................11 2.1 Standards................................................................................................................................................... 11 3 User Requirements Specification................................................................................. 13 4 Types of Controlled Temperature Chamber............................................................... 15 4.1 Freezers.....................................................................................................................................................15 4.2 Refrigerators...............................................................................................................................................16 4.3 Cold Rooms................................................................................................................................................16 4.4 Stability Chambers, Incubators/Incubator Shakers....................................................................................17 5 Commissioning................................................................................................................19 5.1 Scope of the Commissioning......................................................................................................................19 5.2 The Commissioning Strategy.....................................................................................................................20 5.3 Commissioning Activities at the Design Phase...........................................................................................22 5.4 Commissioning Activities during the Installation Phase..............................................................................23 5.5 Handover, the System Manual, and Training..............................................................................................26 5.6 Safety.........................................................................................................................................................26 6 Testing Strategy............................................................................................................. 27 6.1 Outcomes...................................................................................................................................................27 6.2 Risk Assessment........................................................................................................................................27 6.3 When to Perform Temperature Mapping....................................................................................................28 6.4 Factors Influencing the Mapping Strategy..................................................................................................29 7 Qualification................................................................................................................... 35 7.1 Qualification Considerations.......................................................................................................................35 7.2 Qualification Science and Risk-Based Approach.......................................................................................36 8 System Monitoring......................................................................................................... 37 8.1 Temperature Sensors.................................................................................................................................37 8.2 Number Required and Location of Monitoring Probes...............................................................................38 8.3 Considerations for Permanent Sensor Placement.....................................................................................39 8.4 Thermal Dampening Fluids for Temperature Monitoring Probes................................................................40 8.5 Determining Alarm Set Points and Alarm Delay Settings...........................................................................41 9 Periodic Evaluation and Frequency of Thermal Mapping Studies......................... 43 9.1 Handling Excursion Documentation...........................................................................................................48 10 Operational Issues.........................................................................................................49 10.1 Challenging the Area with Operational Activities........................................................................................49 10.2 Open Door Recovery Test..........................................................................................................................49 10.3 Power Outage/Thermal Degradation Test (recovery from power failure or power interruption)................. 49 [PAGE 8] Controlled Temperature Chamber Mapping and Monitoring 11 Packaged Transport Systems........................................................................................ 51 11.1 Active Shipping Containers: Unit Load Devices.........................................................................................51 11.2 Temperature Controlled Trailers.................................................................................................................54 11.3 Trailer Design.............................................................................................................................................54 11.4 Insulation Degradation................................................................................................................................55 11.5 Trailer Validation Approach.........................................................................................................................55 11.6 Trailer Loading Patterns.............................................................................................................................56 12 Maintenance.................................................................................................................... 57 12.1 Cleaning of the Coils..................................................................................................................................57 12.2 Check the Condensate Pipework...............................................................................................................57 12.3 Functional Testing of the Unit Coolers/Defrost Elements...........................................................................57 12.4 Leak Testing...............................................................................................................................................57 12.5 Thermal Scanning......................................................................................................................................58 12.6 System Alarms............................................................................................................................................58 13 Appendix 1 – Example User Requirements Specification.........................................61 13.1 URS Typical Content..................................................................................................................................61 13.2 Sample URS...............................................................................................................................................65 14 Appendix 2 – Sample Document: Number and Location of Mapping Sensors.... 73 14.1 Introduction.................................................................................................................................................73 14.2 Approach....................................................................................................................................................73 14.3 Sensor Placement......................................................................................................................................74 14.4 Monitoring System Sensor Placement.......................................................................................................74 15 Appendix 3 – Example Use of Measurement Uncertainty....................................... 77 16 Appendix 4 – Sample Report Recommending the Location for Freezer.............. 83 16.1 Introduction.................................................................................................................................................83 16.2 Product Temperature..................................................................................................................................83 16.3 Discussion..................................................................................................................................................86 17 Appendix 5 – Science and Risk-Based Development and Use of the Risk Assessment......................................................................................... 87 17.1 Defining the Risk Assessment Process......................................................................................................87 17.2 Scoring the Risk Assessment.....................................................................................................................89 18 Appendix 6 – Example Testing Strategies..................................................................91 18.1 Example 1: Mapping Strategy for a Walk-in Conditioned Space................................................................91 18.2 Example 2: Mapping Strategy for a Refrigerator........................................................................................93 18.3 Example 3: Warehouse Mapping Layout and Rationale............................................................................95 18.4 Example 4: Test Document/Protocol..........................................................................................................98 19 Appendix 7 – Templates and Attachments................................................................ 99 19.1 Example Science and Risk-Based Approach for Periodic Review of a Controlled Temperate Chamber... 99 19.2 Example Job Hazard Analysis Worksheet................................................................................................103 20 Appendix 8 – References.............................................................................................107 21 Appendix 9 – Glossary................................................................................................ 109 21.1 Acronyms and Abbreviations....................................................................................................................109 21.2 Definitions................................................................................................................................................. 110 [PAGE 9] Controlled Temperature Chamber Mapping and Monitoring Introduction A Controlled Temperature Chamber is defined as a system, unit, equipment, or room in which the environmental conditions (usually temperature) of a chamber are controlled/maintained/regulated to meet specific user requirements. The ISPE Good Practice Guide: Controlled Temperature Chamber Mapping and Monitoring expands on the ISPE Concept Paper on Controlled Temperature Chamber Mapping [1] to include topics such as: • Commissioning • Testing strategies • Acceptance criteria • Qualification approaches • System monitoring • Operational issues • Periodic review
With the increasing complexity of global distribution for medicines requiring controlled temperatures and the recently introduced regulations, the ISPE Good Practice Guide: Controlled Temperature Chamber Mapping and Monitoring was developed by an industry team in order to provide guidance on good practices for the definition of the requirements (producing a user requirements document), design, purchasing, commissioning (including temperature mapping), qualification and maintenance of controlled temperature chambers, warehouses, and refrigerated storage areas used to store raw material, work in progress, or finished product, and which operate under current Good Manufacturing Practice. The approach described is consistent with that described in the ISPE Good Practice Guide: Cold Chain Management [2].
This Guide provides guidance on Controlled Temperature Chambers operating under Current Good Manufacturing Practices (CGMPs). Types of Controlled Temperature Chambers considered by this guide include purchased “commercial off the shelf” items (such as freezers, refrigerators, and incubators), warm rooms designed to maintain consistent temperatures, ovens, and custom built units, such as controlled room temperature environments, e.g., warehouses, walk-in cold rooms and freezers. This Guide does not include systems designed for heating/cooling of material such as blast freezers, although some of the concepts described may be useful when commissioning/ qualifying these systems. [PAGE 10] Controlled Temperature Chamber Mapping and Monitoring
There is an increased regulatory interest in cold chain driven by the growing number of products requiring controlled temperature shipping and storage, the complexity of the distribution network for the products and governmental requirements for distribution of vaccines. This is reflected in the recent revisions to the related regulatory guidance (see Section 1.4). Utilizing this Guide provides a number of benefits in an area where there is little authoritative guidance, including: • Provision of industry good practice for the temperature mapping of controlled temperature chambers, considering the impact of load, and the use of the data to determine the location and number of monitoring sensors • Development of test acceptance criteria • A risk based approach to practices for periodic review of system performance
Regulatory guidance covering Controlled Temperature Chambers issued or updated at time of publication includes:
Health Products Regulatory Authority (HPRA) (previously the IMB): Guide to Control and Monitoring of Storage and Transportation Temperature Conditions for Medicinal Products and Active Substances [4]
European Medicines Agency (EMA), Guidelines of 7 March 2013 on Good Distribution Practice of Medicinal Products for Human Use [5]
PIC/S Guide PE 011-1 to Good Distribution Practice for Medicinal Products [6] Also see:
European Commission, Guidelines of 5 November 2013 on Good Distribution Practice of Medicinal Products for Human Use [7]
Health Canada, Guidelines for Temperature Control of Drug Products during Storage and Transportation (GUI-
MCA Part II, Chapter 6, Control and Monitoring of Storage and Transit Temperatures [10] There is also guidance in the United States Pharmacopeia (USP):
USP <659> Packaging and Storage Requirements [11] [PAGE 11] Controlled Temperature Chamber Mapping and Monitoring
Commissioning A well planned, documented, and managed engineering approach to the start-up and turnover of facilities, systems, and equipment to the End-User, that results in a safe and functional environment that meets established design requirements and stakeholder expectations [12]. Qualification Activities undertaken to demonstrate that utilities and equipment are suitable for their intended use and perform properly. (FDA) Rounding of Temperature Values This Guide follows USP <32> Section 7.20 Rounding Rules when considering temperature values: “When rounding is required, consider only one digit in the decimal place to the right of the last place in the limit expression. If this digit is smaller than 5, it is eliminated and the preceding digit is unchanged. If this digit is equal to or greater than 5, it is eliminated and the preceding digit is increased by 1.” [13] [PAGE 12] [PAGE 13] Controlled Temperature Chamber Mapping and Monitoring 2 Related Standards Regulatory guidance for Good Distribution Practice (GDP)1 is updated on a regular basis. There is normally a requirement to demonstrate that product is being stored in the appropriate conditions. This can be accomplished through the mapping that all storage locations used in the Controlled Temperature Chamber remain within the defined conditions.
Which environmental conditions are critical, e.g., light/temperature/humidity? Qualification is intended to demonstrate through testing (verification) that the requirements specified in the URS have been met. Confirmation that the user requirements have been met should be traceable in the qualification documentation. Appendix 1 provides discussion of typical content and an example of a URS for a cold room. Note: information included in specifications or the purchase order general requirements (such as manuals, training, spare parts) are not included in the URS to avoid duplication; the URS should be a simple concise definition of the user requirements. For a standard “catalogue” item, the URS may be developed in the form of the purchase order. [PAGE 16] [PAGE 17] Controlled Temperature Chamber Mapping and Monitoring 4 Types of Controlled Temperature Chamber
Freezers are used for short to long term preservation of pharmaceutical and biopharmaceutical materials, e.g.: • Active Pharmaceutical Ingredients (APIs) • Process intermediates • Stability samples • Laboratory materials • Cell banks Temperature uniformity is maintained within a qualified range to ensure product quality is preserved. Freezers with set points ranging from -20°C to -80°C (-4°F to -112°F) are frequently used. Operation can be controlled via a temperature controller that is used to maintain the locally configured temperature set point and also provides a local alarm. Manual defrost chambers are usually equipped with the general freezer refrigeration components of: • Compressor • Receiver • Condenser • Evaporator • Tubing • Insulation • Structural support The refrigerant compressors are usually hermetically sealed for integrity. The evaporator is typically a tube and fin design. The chamber control monitors interior temperature using a permanently installed thermocouple or Resistance Temperature Detector (RTD) (referred to within this guide as the control probe). Typically, the control probe is calibrated at the factory based on the temperature at the geometric center of the chamber. The evaporator is usually located within the upper portion of the chamber interior and chamber temperature uniformity is obtained through natural air circulation. There are several different designs available, as well as units cooled by a Stirling engine. For units with an automatic defrost, the control actuates an automatic defrost cycle at a predetermined frequency (typically 6 to 24 hours) to minimize ice accumulation. The evaporator defrost generally occurs by re-directing the hot refrigerant gas into the evaporator coil for a short time to melt any ice/frost accumulation. Depending on manufacturer and model, the defrost cycle is terminated by: • Elapsed time [PAGE 18] Controlled Temperature Chamber Mapping and Monitoring • Evaporator coil temperature set point • A combination of time and temperature The frequency of defrost is adjustable to allow for the conditions of use (frequency of door openings, length of time for door openings, and exterior air humidity level at time of door opening). The defrost cycle can usually be adjusted. For GMP applications these systems should be monitored by an independent system. It can be difficult to calibrate the system control sensor, and the use of an independent system allows routine calibration, and the flexibility to place the sensor in a location that measures the “worst case” temperature.2 This system is used as the quality “system of record” to provide the data used to demonstrate that materials are being stored at the specified conditions. 4.1.1 Conditioning/Blast Freezers Facilities may process large quantities of bulk product that needs to be frozen from ambient conditions to a specified temperate, e.g., -70°C (-94°F) prior to transfer into -70°C (-94°F) storage locations. Dedicated conditioning freezers are needed to perform this function, as storage freezers are not capable of handling the large volume of product and significant temperature disparity, without potentially compromising the temperature of the stored material. This type of equipment is outside the scope of this guide.
Used for storage of material below -120°C (-184°F), e.g., cell banks. If materials are immersed into liquid nitrogen, they eventually assume the temperature of the liquid (-196°C (-321°F)). Materials stored in the vapor above the liquid become warmer as they are moved away from the liquid (up to -120°C (-184°F)). The temperature of the vapor can be changed by varying the amount of liquid nitrogen in the chamber.
Refrigerators are typically used to store material and vaccines within a qualified range of 2°C to 8°C (36°F to 46°F). The capability of the equipment to achieve temperature uniformity should be considered when assigning the chamber set point. Operation is typically controlled via a temperature controller that is used to maintain the locally configured temperature set point, and may also provide a local alarm. Refrigerators may be equipped with fans which cool via forced air circulation and utilize a hermetically sealed compressor and refrigeration system. Alternatively, refrigerators may use a heat exchanger located in the storage space, relying on convection to maintain an even temperature. Refrigerators should have wire shelving to improve air circulation. Refrigerators will usually automatically defrost the evaporator to maintain system performance. Evaporator defrost occurs by re-directing the hot refrigerant gas into the evaporator coil for a short time to melt any ice/frost accumulation.
Cold rooms are typically used for storage of material within a qualified range of 2°C to 8°C (36°F to 46°F). Cold rooms should be equipped with a refrigeration compressor/condensing unit. The air-cooled condensing unit is usually located outside, e.g., on the roof of the building. Cold rooms may be provided with redundant condensing systems, each capable of handling the total system load. 2 That which is closest to the acceptable operating limits/the acceptance criteria. [PAGE 19] Controlled Temperature Chamber Mapping and Monitoring Walk-in cold rooms may be prefabricated, metal-clad structures, furnished and installed as self-contained units. These may include all essential refrigeration equipment, controls, air circulation, and other equipment necessary to reach the specified environmental conditions. Cold room control systems usually consist of a local Programmable Logic Controller (PLC) to monitor and control the temperature within the cold room. Within the main chamber, the temperature may be measured by temperature sensors placed in different locations. One sensor should be routed to the main controller for controlling interior temperature. The second sensor should be connected to a monitoring system for temperature trending and alarm; for larger units there may be multiple monitoring sensors.
Stability chambers are chambers that are designed to maintain a stable environment for incubating materials or holding samples. These may include cultures for microorganisms or cell culture and hybridization in production or Quality Control laboratories. The incubator may accommodate cell culture vessels from small tissue culture flasks to roller bottles and small spinner flasks. A local controller should control system operation for process parameters such as temperature, humidity, and CO2. Incubator shakers can also control shaker speed (Revolutions Per Minute (RPM) of the drive). [PAGE 20] [PAGE 21] Controlled Temperature Chamber Mapping and Monitoring 5 Commissioning
The commissioning process should be a well-planned, documented, and managed engineering approach to the start- up and turnover of both the system and the equipment to the End User. Commissioning should result in a safe and functional environment that meets established design requirements and stakeholder expectations (see also the ISPE Baseline® Guide: Commissioning and Qualification [12]. The complexity of commissioning can vary, depending on the type of system. If a risk-based approach is being used, the commissioning documentation may be used to provide evidence of the installation and operation. The commissioning documentation needs to be of an acceptable standard. Typical expectations for the commissioning documentation are provided (see Section 6). Units used for stability testing or laboratory storage are usually Standard “Catalogue” Systems.
Standard “Catalogue” Systems are comprised of mechanical components assembled and/or produced by a manufacturer for general industry applications. There is a limited standard menu of options with respect to hardware and/or software. A manufacturer normally provides a standard operations manual that applies to the operation and maintenance of the system. Standard “Catalogue” Systems are usually set to work following the manufacturer’s instructions. Examples of Standard “Catalogue” Systems include freestanding freezers and refrigerators. Commissioning is usually simpler for standard catalogue equipment, as the control system is an integrated part of the standard catalogue system, with data on all the components contained within the supplier documentation. A typical commissioning approach could follow the steps listed below: • Recording of system data • Verification of correct installation (installation verification) • Confirmation of satisfactory operation/temperature mapping (operational verification) Note: the approach described assumes that the unit is to be used to store GMP material. Generally, Standard “Catalogue” Systems have been set up in a factory by the manufacturer; typically, the scope of work does not include mapping, this is usually added to the vendor’s requirements.
Site (Custom) Built Systems normally require additional verification to ensure that operation is as specified, usually with more adjustment (set up and tuning) of the refrigeration and associated control systems, in order to ensure that performance meets the user requirements and design specifications. [PAGE 22] Controlled Temperature Chamber Mapping and Monitoring
The testing strategy and the acceptance criteria should be documented in a Commissioning Plan prior to test execution. The objective is to: • Show that the work will meet Owner and regulatory agency expectations • Provide clear and early definition of deliverables and handover requirements • Define roles and responsibilities • Define the Engineering Change Management System • Define the approach to be used for training of the maintenance department and End Users • Ensure consistency of approach and testing across the project • Ensure full transparency on progress metrics (test execution and productivity) • Scope the testing required • Provide review and approval of test method statements • Provide progress reporting • Provide reporting and handling of test discrepancies • Define the location and marking (identification) of mapping points • Define the acceptance criteria/expected results3 • Witnessing requirements and notification procedures • Handling/retention of raw data • Format and content of the commissioning report (e.g., is a particular documentation practice required?) • Defined responsibilities for operating and maintaining a facility during commissioning, until it is handed over to the End User • Identify who is responsible for maintaining the operating log for the system from start-up to handover • Define how is handover to be managed The Commissioning Plan should also define how safety is considered. When executing the plan, Commissioning and Qualification may be performed in two distinct phases, or the phases can be combined. For more information, see Chapter 7 on Qualification. 3 Note: acceptance criteria are “non-negotiable” test results, expected results may be acceptable across a broader range, or are results taken for reference purposes. [PAGE 23] Controlled Temperature Chamber Mapping and Monitoring
The Commissioning Plan should contain a section which clearly states required roles and responsibilities. The roles should be designated and authorized in the Commissioning Protocol. Typical roles and responsibilities of parties involved include: • Commissioning Lead • System Owner • Commissioning Team Member • Engineering/Technical Services and Validation Group Appropriate training for each role should be provided prior to participation in commissioning where necessary. Commissioning Lead Party responsible for coordinating and managing commissioning activities and allocating resources. The Commissioning Lead takes ownership of the activity, writes and/or executes the activity, and is responsible for the accuracy of the content. System Owner Party that reviews the content of the document, and by signing the Commissioning Plan and Test Report, agrees to the content. The System Owner has decision making authority and is accountable for the compliance to the URS. During the design phase, the System Owner should be in charge of design activities and, during construction, they should determine acceptance of the “as built” system at mechanical completion. The System Owner may be a representative of the project team, or the role may be delegated to a Subject Matter Expert (SME). Commissioning Team Member Party involved in the activity (execution, documentation, and expertise). Commissioning Team Members may be organization employees or contractors. The work can be divided into two categories: • Site activities: verification of completion of the systems presented by the construction team or manufacturer, performance of job safety analysis, execution of protocols, compiling of protocols, submission of punch items, and training of the maintenance team • Office activities: preparation of the commissioning test documents, updating of construction documents as red marked during the commissioning phase, communication of executed protocols to the team, performance of archiving Engineering/Technical Services and Validation Group Party copied on the official distribution list of the document, but not considered to take any action in relation to the commissioning document; they may review as SMEs. [PAGE 24] Controlled Temperature Chamber Mapping and Monitoring
From the commissioning perspective, the Design Review is intended for the commissioning team to become familiar with the project and to verify that the design has adequate provision for the tests required, as defined in the equipment specification and URS. Requirements in the URS should be clarified with attendees. Key design documents should then be reviewed. Issues relevant to continuous operation of the Chamber are critical aspects to consider and include: • Chamber loading scenarios • Loading and unloading of products • External/adjacent environmental conditions Typical documents for verification include: • Layout a Heating, Ventilation, and Air Conditioning (HVAC) zoning lay out • Room environmental parameter schedule • Piping and Instrumentation Diagram (P&ID) • Functional specifications During the Design Review phase, documents relevant to the areas surrounding the chamber and to the utilities serving it (e.g., hot water, chilled/glycol water (heat transfer fluids), electricity) should be included in the review in order to properly understand the interaction between the Controlled Temperature Chamber and the rest of the facility. The Commissioning Team should define the list and sequence of at site activities and verifications needed, and complete the Commissioning Plan. A tailored approach is usually required as the sequence and activities are dependent upon the specific site conditions, utilities available, operating conditions and type of Controlled Temperature Chamber. In this phase or in the detail design phase, the Commissioning Team should be given opportunity to provide suggestions to the designer, in order to obtain a design that will facilitate Commissioning Tests and activities. Suggestions may include availability of access to regulation points, provision of testing points in an appropriate location, or access ports to the room for installation of cabling, if required during temperature mapping.
A risk assessment may be used to help critique and develop a robust design. A Failure Mode Effects Analysis (FMEA) risk assessment can be used to identify possible failures that could lead to the loss of the required performance and may be identified by review of design and vendor documentation. Risks should be evaluated as to their probability and severity, in order to determine the impact to process variation and effect. Unacceptable risks should be mitigated following the preferred hierarchy of: • Elimination by design [PAGE 25] Controlled Temperature Chamber Mapping and Monitoring • Elimination by automated control • Elimination by procedural controls The risk management requirements identified should be designated as critical and include all components, functions, and features of the design that serve, collectively or singly, to control risks. These functions and features should be tested during commissioning.
Commissioning activities may be divided into four broad categories:
Pre-operational safety checks
Setting to Work, defined as setting a static system into motion or “shake down” and regulation and adjustment
Functional testing: regulation, adjustment, and functional testing may be iterative activities within fine tuning of the system
The Commissioning Team scope should include confirmation that: • The equipment and materials are checked to ensure compliance with design data sheet and specifications • Installation has been completed in accordance with the design specifications and manufacturer instructions • As-built documentation is available and correct The approach to inspection of the physical installation may vary depending on the type of Controlled Temperature Chamber. Usually, 100% of the installation is verified (packaged units (such as the compressor) would be considered as a single system component). It is usually a duty of the Commissioning Team to maintain a “red line”4 copy of the construction record documents. Comments and changes should be marked on the document following a defined procedure, to be turned over to the responsible party for updating the record documents to be provided to the System Owner. Some of these activities may be performed at the vendor’s factory and documented within specific Factory Acceptance Test (FAT) protocols/reports. Completion of this stage should verify that the installation meets specifications.
This phase is intended to eliminate as many risks as possible in regard to the safety of personnel during the commissioning and also during operation. A section of the Commissioning Protocol (or site acceptance test) will describe and document appropriate procedures. 4 These mark ups are traditionally done using a red pen, hence the term “red line”. [PAGE 26] Controlled Temperature Chamber Mapping and Monitoring Procedures such as the “Lock Out/Tag Out” procedure can determine that utilities, e.g., chilled water/gas/steam and electrical power, are provided to the system once the following are available and documented: • Conformity of electrical system included in the Controlled Temperature Chamber system and correct settings e.g., overloads/fuse ratings • Evidence of pressure test of utilities lines • Presence of pressure/temperature safety release devices (with right set)
This is the initial startup and tuning of the system. This may include: • Energizing the system • Filling with fluids • Check motor drives – mechanically electrically (fuse/overload rating insulation) and direction of rotation checks • Internal Layout of the Chamber verification and as-built dimension measurements • Chamber and doors tightness verification • Input/Output (I/O) check of the control system • Alarms check • Calibration of the instruments • Balancing and fine tuning
Checks performed in previous phases should have been executed successfully as a prerequisite to functional tests. The system should be tested to confirm that the design performance is achieved within the acceptance ranges specified in all working modes. Where feasible, the worst case5 conditions for the surrounding environment should be simulated during testing. Alternatively, the conditions during testing for the surrounding environment should be recorded and the performance of the system should be assessed to ensure that it meets expectations for those conditions. For example, external conditions can impact the performance of a condenser or cooling tower; this data should be reviewed to ensure that it aligns with the user requirements in relation to the temperature/humidity. Where the area being tested has duty/standby conditioning units (systems), these should both be tested to ensure that they will perform adequately. Studies of trends of the transition phase between the stop of the main system and the full operation of the standby system should be included in testing. 5 The most extreme conditions defined in the URS and which will provide the worst case challenge for the conditioning system. [PAGE 27] Controlled Temperature Chamber Mapping and Monitoring The operation and influence of the surrounding environment on defrosting systems should be verified and documented during the Commissioning and Qualification Phase.
It is a good practice to manage changes, in order to ensure that:
Lessons learnt from previous equivalent systems are incorporated
Risks specific to the way the system will be used are mitigated to an acceptable level through the design
The user corporate and GMP requirements have been met.
Handover usually represents turnover of the system to the user, with handover of operation and maintenance. Commissioning and Qualification activities are usually completed. (The timing of handover may be defined differently on a case-by-case basis according to specific contract stipulations). There should be a documented record confirming that the functionality and operation of the system is considered acceptable and Commissioning can be considered complete. This may be the Commissioning or Qualification Summary Report, or a separate handover certificate, depending on site practices. A punch list (snag list) is typically used to manage completion of the system to meet the specifications. Major items on this list would prohibit handover, other items that can be resolved following handover are generally accepted. These items should be included on an action list to facilitate tracking their completion after handover. Typical categories used for a punch list include:
Items that affect safe operation of the equipment – to be addressed prior to handover
Items that block next activities/verifications – to be addressed prior to handover
Minor items that do not impact operation – to be addressed after handover
Desirable changes/improvements – to be addressed after handover through the change control system Following handover, responsibility for operation and maintenance of the system should be transferred to End Users and the maintenance team. Appropriate operation and maintenance procedures should be established.
A job safety analysis covering all the phases of commissioning should be prepared by the personnel who will execute the site activities. The analysis should describe the potential risks, their probability, and should identify protection devices. Operators or technical personnel should be informed about the outcome of this analysis when receiving permission to execute commissioning activities. Information about scheduled activities and related risks should be provided to other personnel that may be in the area at the same time. The job safety analysis should be reviewed by the personnel responsible for safety. An example job hazard analysis template is provided in Appendix 7. When judged appropriate, the testing area or room should have signs informing personnel of risks or forbidding access. [PAGE 29] Controlled Temperature Chamber Mapping and Monitoring 6 Testing Strategy
Testing is intended to:
Determine locations representing operating temperature extremes to establish the strategy for monitoring and alarming the space used for storage and/or processing The operational temperature limits should be defined, together with any allowable excursions (time periods, acceptable limits).
Prior to developing the test strategy, evaluate potential sources of excursions taking into account the following factors. (Note: a company may use Computational Fluid Dynamics (CFD) modeling to evaluate impact of these factors but still needs some level of confirmation of the results through actual testing.)
Size: speed and magnitude of changes impacted by the footprint as well as the height with attention to potential stratification with heights over 15 ft (457 cm)
Layout/configuration: wall and obstructions, fixed racks, temporary racks, pallets on floors, duct supply and return locations
Location of facility: geographic with respect to external climate exposures, physical location within temperature controlled facility, windows, doors, traffic and access frequency
Operating characteristics of the HVAC system: defrost cycles, redundant systems, number of units supporting storage space and how they interact with each other
With the advent of ASTM-E2500 “Standard Guide for Specification, Design, and Verification of Pharmaceutical and Biopharmaceutical Manufacturing Systems and Equipment” [21] an organization may use a risk-based approach, with the equipment installation and operation being verified. For further information, see:
The ISPE Guide: Science and Risk-Based Approach for the Delivery of Facilities, Systems and Equipment [22] Also see Section 7. There should be a clear definition of the acceptance criteria; typically, this is provided in the URS or equivalent document. Temperature mapping is used to confirm that the system is operating to meet specifications i.e., the temperature range within the unit is acceptable. [PAGE 30] Controlled Temperature Chamber Mapping and Monitoring It is a standard practice in the pharmaceutical industry to provide monitoring of critical parameters using an independent system. Advantages of this practice include: • Calibration of the monitoring sensors can be carried out without impacting the system operation • The independent system becomes the quality “system of record” • The data can be used to provide continuous verification of acceptable system performance Mapping results may be used to define the number and location of monitoring sensors for a warehouse, cold room, or chamber.
Temperature mapping should start as early as possible during commissioning. This allows the early detection and resolution of any performance issues. It also allows potential operational constraints to be identified and discussed with End Users, to determine if the constraints are acceptable or require resolution. Where there are systems that support operation of a system e.g., the warehouse, HVAC system, or a condenser water cooling system, these systems should be identified and be commissioned or in a known (and monitored) state prior to temperature mapping, to help ensure complete and representative testing, and facilitate investigation in the event of performance problems. For example: It can be acceptable to temperature map an area served by an HVAC system where a chilled water system which supports HVAC system operation has not been fully balanced, if: • the chilled water system is known to provide an adequate supply of chilled water at a constant temperature Note: the Building Management System (BMS)/Building Automation System (BAS) could be used to provide supporting data that: • the chilled water supply temperature remains within the operating limits • the HVAC system cooling control valve does not open completely – indicating that an adequate supply of chilled water has been available for the duration of the test [1]
Before temperature mapping commences, the commissioning plan/temperature mapping strategy should be approved by the Quality Unit. The level of detail, number of personnel, or number of suppliers involved in temperature mapping can vary depending on the type of project. For example, commissioning of an air conditioned warehouse in a new facility can involve several groups (e.g., construction manager, system installation contractors, commissioning contractors). For a custom built refrigerated storage room purchased through a design/build qualify contract, the requirements and responsibilities may lie with one company. Temperature mapping equipment should be calibrated. Documents which should be available from the supplier/construction company (as applicable), include: • Control System I/O list [PAGE 31] Controlled Temperature Chamber Mapping and Monitoring • Control System Drawings (e.g., control panel layout, wiring diagram) • Equipment and instrument lists • Materials receiving and inspection reports/material certifications • Equipment receipt and/or installation verification records • Cable tests (continuity, insulation) • Grounding (earth) tests • Motor insulation “megger” and direction of rotation tests • Fuse and breaker ratings/overload settings • Control loop wiring checks • Piping leak (hydrostatic) and evacuation tests • Pipework cleaning/flushing records • Record of cleaning for ductwork • Ductwork and Air Handling Unit (AHU) leakage tests • Operation and Maintenance manuals • As built drawings/specifications The test requirements will depend on the type of system, and how critical performance is to the product and/or business. Project specifications should define documentation and test requirements.
Adequate space should be provided for cleaning for walk-in cold rooms, freezers, and warehouses, but a mobile load may be stored in the space • Storage locations for standalone units should follow manufacturers’ recommendations to ensure adequate space inside for air movement • Buffered probes may be used for monitoring if the performance relationship is known compared to the characteristics of the stored product characteristics • Buffered probes should not be used as controlling probes; the buffer provides a response delay usually of a short duration to allow for temperature upsets due to defrost, door openings, etc. • Buffered probes should not be used for mapping when the goal is to see the actual room temperatures • Type of probes: accuracy, reliability, ease of use and calibration (all impact measurement uncertainty which must be incorporated in mapping and monitoring/alarming practices • Probe locations: number of probes, distance between probes, usable space, direct path of air stream, proximity to coils (during cooling/defrost), doors, windows, heat sources (motors, lights, product being cooled) • Sample rate: at least once every 5 minutes; may need to be more frequent if spikes in temperature anticipated due to cycling of defrost, cooling, access that cannot be tolerated by the material stored • Operational requirements: how long doors open, how many people, traffic patterns, equipment • Operation of an aspirating smoke detection system
Selection of the equipment to be used for mapping should consider the required accuracy and repeatability related to the predefined acceptance criteria, e.g.: [PAGE 33] Controlled Temperature Chamber Mapping and Monitoring A unit may have acceptance criteria of 2°C to 8°C (35.6°F to 46.4°F), (standard storage conditions per USP). If the mapping system has an accuracy of ± 0.5 °C these provide results (allowing for rounding of the results) to meet the acceptance criteria of 2°C to 8°C (35.6°F to 46.4°F). The user requirements may have a tighter design specification, i.e., expected results of 3 to 7°C Some low cost mapping dataloggers have accuracy specifications of ± 2°C. Use of these devices would not be appropriate for this application unless the acceptance criteria or expected results were revised to allow for the potential error. Temperature sensors with a rapid response time are typically used for temperature mapping, to help to provide accurate information on system performance: • If humidity has been defined as a critical quality attribute • If there are no significant sources of humidity in the warehouse, it may be assumed that absolute humidity will equalize within the warehouse – use of a small number of sensors may be all that is required to provide the required data – one at a low level and one at a high level (in case of stratification) • If there are significant sources of moisture, then the humidity could vary significantly within the conditioned space, and a greater number of humidity mapping sensors will be required – the number and location can be developed using similar concepts to those used for the temperature mapping Where Relative Humidity (RH) is the criteria, the levels should be checked based on temperature variations using the measured RH at the local temperature from the mapping sensors to determine the RH in the rest of the space. Using duplex sensors (where available) can simplify the data analysis. Mapping sensor locations should be documented, to allow a test to be repeated if necessary. The proposed load test strategy should be reviewed and approved by the Quality Unit and the System Owner.
The diagram on the left of Figure 6.1shows the suggested minimum number of mapping sensor locations to be used for a system with a chamber volume up to approximately 70 cubic feet (2 cubic meters). The diagram on the right of Figure 6.1 shows the minimum number of mapping sensor locations suggested for a system with a chamber volume of up to 700 cubic feet (20 cubic meters).
[Figure 6.1: Example Sensor Locations]
Note: the inner box represents the working area (where product is stored), the circles represent the sensor locations. [PAGE 34] Controlled Temperature Chamber Mapping and Monitoring The sensor locations used for mapping should be defined based on: • Where product will be stored • The potential major influences on the internal conditions during use • The number and location of heating/cooling units • For units used for conditioning, the unit should have the capacity to condition components within the desired time and temperature per the user requirements – sensors should be in the load • Defrost cycles should be considered when outlining test procedures. Defrost temperature ranges and alarms should be defined according to user requirements or chamber profile Table 6.1: Recommended Placement of Measuring Devices Location Rationale Adjacent to temperature sensor used for Controlled Temperature Chamber monitoring Ensures that the Controlled Temperature Chambers monitoring probe is correctly monitoring the set parameters Storage rack corners including geometric center of rack Ensures that the furthest locations can maintain temperature and that the distribution temperature is met and maintained Storage locations adjacent to ingresses/ egresses (Door) A potential area for temperature deviation Storage locations near Air Supply and Return Outlets To monitor air temperature within proximity to air inlets and outlets Storage locations near Air Distributors (i.e., fans, blowers, etc.) Ensures that the air distributors do not create temperature excursions or dead air pockets that may impact component temperature, or cold spots where they blow onto stored material Shelving Ensures that the type of shelving structure does not create dead air pockets leading to temperature deviations Storage locations adjacent to physical or structural obstructions Ensures that the structures within the Controlled Temperature Chamber do not create dead air pockets leading to temperature deviations Height of component storage Ensures that the intended height of component storage is monitored at the maximum height of any potential material to be stored Storage locations adjacent to physical or structural obstructions Ensures that the light does not create warm spots, when turned on that may impact component temperature There should be a scientifically based rationale developed for the number and location of the sensors; however, there are some basic requirements: • For a system with external walls (e.g., a warehouse) or where the system performance can be influenced by external conditions (e.g., where the refrigeration system uses an air cooled condenser), data should be available on the external conditions. This data may originate from another calibrated reference source e.g., the Building Management System (BMS)/Building Automation System (BAS) (not the mapping system). This is to show the relationship of the conditions at the time of testing with the design temperature range, allowing the designer to evaluate the data. [PAGE 35] Controlled Temperature Chamber Mapping and Monitoring • For a conditioned room or Standard “Catalogue” System within a facility/room, there should be data on the facility/room conditions at the time of testing outside the store, to ensure that any open door tests are representative of normal operating conditions. The data could be provided by an independent calibrated system or a sensor included in the mapping system. • Where appropriate there should be a mapping sensor adjacent to the system control sensor (this may not be practical if the control is from a number of sensors that are being used to calculate an average temperature). When defining the number of sensors and their locations, factors to consider include: • The mapping sensor locations should be increased as necessary to monitor areas where changes in the conditions are likely to be found during use, e.g., conditions for product located near a conditioned air discharge. • Where there are multiple air conditioning units or HVAC outlets which operate consistently, the area treated by each unit may be treated as a zone, with the mapping sensor layout developed to suit those zones. • An area may be laid out so that it can be divided into zones that will perform similarly e.g., there may be end zones, and internal zones. Temperature mapping a representative zone may provide adequate data to represent performance of the whole area. • Where appropriate, there should be a mapping sensor adjacent to the system control sensor. This allows interpretation of the system performance compared to the temperature experienced by the control sensor (Note: this may not always be practical, e.g., if the control signal is obtained from a number of sensors located throughout the space that is being used to determine the unit average temperature) A rationale that describes the location and number of sensors to be used should be developed. This should be reviewed and approved by the Quality Unit and the area/System Owner. Note: general guidance should not be used without a supporting rationale e.g., there should be a sensor every 4 m. If the area being mapped has no factor that could cause a change in the temperature, multiple sensors to monitor the same effects would be redundant. [PAGE 36] [PAGE 37] Controlled Temperature Chamber Mapping and Monitoring 7 Qualification Systems considered to have the potential to impact product quality require Qualification. This will include systems used to store GMP raw materials, intermediate, and finished product. Where the temperature of individual gel packs used for shipping is verified before they are used (confirming system performance/adequate pack conditioning time), the systems used for conditioning and storing them may be categorized as engineering systems (i.e., commissioned systems). The decision to Commission or Commission and Qualify is a judgment based on a comprehensive understanding of the product, process, and the nature of the system by appropriately qualified personnel. See the ISPE Baseline® Guide: Commissioning and Qualification [12]. The traditional approach used for Qualification uses separate protocols to provide documented evidence that the installation (Installation Qualification (IQ)) and operation (Operational Qualification (OQ)) meets the user requirements/system specifications after commissioning has been completed. IQ and OQ may be combined into a single document and reference (leverage) the commissioning tests that demonstrate compliance with the requirements. Typically, a system Performance Qualification is not required, any operational testing required may be addressed in OQ.
• IQ should include a record of the major components, confirmation that calibration has been conducted as required by the specifications, confirmation that the specified utilities have been correctly connected • OQ testing should provide evidence that the system temperature ranges meet the specifications during simulated operations. Quality related alarms should be tested • Perform open door testing where applicable • Perform Power Loss Temperature Rise testing where applicable • Temperature mapping should be conducted on an empty chamber for no less than 24 hours • Temperature study shall be conducted on the specified load for no less than 24 hours • Mapping sensors should be located as defined in the test strategy document • The Protocol should include a diagram showing the mapping sensor placement • The level of liquid nitrogen or CO2 is maintained at its set-point (liquid N2 or CO2 freezers) [PAGE 38] Controlled Temperature Chamber Mapping and Monitoring
There are many ways of applying a science and risk based approach to the qualification of a controlled temperature chamber. Examples are provided in Appendix 5. The concept is based on definition of a test strategy, and conducting testing once, with “Qualification” confirming that there is documented evidence that the installation and operation meet the specifications, typically through the engineering documents installation verification and operational verification can be documented through the commissioning/ FAT/Site Acceptance Testing (SAT). For further information, see the ISPE Baseline® Guide: Commissioning and Qualification [12]. [PAGE 39] Controlled Temperature Chamber Mapping and Monitoring 8 System Monitoring It is considered a good practice to use an independent system to monitor the critical parameters. Calibration of the monitoring probes can be performed without impacting system operation. The location of the probes can be determined during mapping. The system used will depend on the customer and may include: • Conventional chart recorders • Datalogging chart recorders • BMS/BAS systems • Supervisory Control and Data Acquisition (SCADA) systems
There are three main types of temperature sensor:
Resistance Temperature Detectors (RTDs) and thermistors
Chemical
Thermocouples work due to the Seebeck effect – when a conductor is subjected to a temperature gradient, it will generate a voltage. Measuring this voltage involves connecting another conductor to the “hot” end, the joint is usually a weld between the two metals, often protected by a thin wall polytetrafluoroethylene (PTFE) sleeve. This additional conductor will then also experience the temperature gradient and develop a voltage of its own which will oppose the original. The magnitude of the effect depends on the metal in use and the extent of the temperature gradient. Using a dissimilar metal to complete the circuit creates a circuit in which the two legs generate different voltages, leaving a small difference in voltage available for measurement. The difference is typically between 1 and 70 µV per degree Celsius (µV/°C) for standard metal combinations and varies according to the temperature difference. The cables and joints can be prone to damage. During validation and commissioning, provision may be made in a test protocol to prevent any effect on the validity of a test (1% is a figure commonly used) by the failure of a sensor or a failure in the recalibrating of a sensor. Care should be taken to ensure that, if a sensor fails, and it is located in a region where results may be unpredictable, it may be advisable to repeat a test run. Thermocouple Accuracy The accuracy of a thermocouple is affected by its type and the operating temperature. See Table 8.1 for the maximum permitted error (in degree Celsius) for various common thermocouples that comply with the International Electrotechnical Commission (IEC) Publication 584 [31]. [PAGE 40] Controlled Temperature Chamber Mapping and Monitoring Table 8.1: Maximum Permitted Errors (in Degree Celsius) for Thermocouples
Resistance Temperature Detectors (RTDs) and Thermisters are available to various grades and manufactured in a variety of housings. The operating principle considers the change in resistance of the sensor as the temperature changes. The change in resistance is measured by passing a small current through the device, measuring the voltage drop using a Wheatstone bridge. An RTD is constructed from metal with the resistance of the device increasing with the temperature. A thermister is made using a ceramic material with the resistance decreasing as the temperature increases. High quality sensors are considered reliable and accurate and may last more than eight years in accelerated life tests, while maintaining the specified accuracy. Various wiring configurations are used to minimize the impact of the cable between the instrument and the sensor, e.g., 3-wire or 4-wire configurations. Accuracies The accuracy of an RTD is defined by its class according to the International Electrotechnical Commission (IEC) Publication 751 [32]; it is affected by the operating temperature: A class A device will be within ± 0.15 degrees C at 0°C (± 0.27 degrees F at 32°F) A class B device will be within ± 0.3 degrees C at 0°C (± 0.54 degrees F at 32°F) There are no international standards for thermisters, but they typically are similar in accuracy to a class B RTD.
There are chemicals that change in color depending on the temperature. These indicators can be used to record the minimum and maximum temperatures. These devices are not considered accurate and normally there is no time record associated with temperature change.
2.5 1.5 1.5 1.5 1.5 1.6 1.6 [PAGE 41] Controlled Temperature Chamber Mapping and Monitoring
Once mapping is complete, the test data should be reviewed to determine the number of permanent monitoring sensors and where they should be located. For small units (less than 2 cubic meters) it may be considered acceptable to use one monitoring sensor located in the worst case location (typically the hottest location for a Controlled Temperature Chamber operating below room temperature), as a single sensor will provide robust detection of any operational or performance issues. For larger systems, or where there are multiple cooling systems, more sensors may be justified to ensure that an adequate record is available for the positions where stored product will experience the maximum and minimum temperatures (and/or maximum or minimum humidity, where applicable) during normal operation. The optimum locations can be determined by reviewing the monitoring data considering periods or tests that represent normal use, e.g.: • Operation in working hours • Operation outside working hours • Loading • Unloading The mapping results and the data analysis can be interpreted and summarized in a report recommending the optimum locations for approval by the Quality Unit and the area/System Owner. Where testing has demonstrated that equipment failure can have a significant impact on local conditions (e.g., where conditioning is provided by a number of independent HVAC units), the data can be used to recommend actions to be taken in the case of such an event, e.g., putting a defined rack out of use. It is considered normal to experience short term temperature excursions due to door opening or personnel and truck movement. There are two approaches normally used to minimize nuisance alarms from these events: • Putting time delays into the alarm system so that an alarm is given only if the temperature has been outside the alarm set point for more than a pre-defined time • Putting the sensor into a container of thermal fluid or equivalent (i.e., buffering). Both of these approaches are intended to provide a simulation of the thermal response time experienced by the stored product due to the packaging acting as an insulator, significantly damping out any short term temperature excursion on the temperature of the stored product. Where this approach is used it should be documented, and include a supporting rationale. Considerations for placement of permanent sensors include: • The results of the mapping of the Controlled Temperature Chamber should determine the number of permanent monitoring sensors and their locations • Risk-based worst-case storage locations • Coverage based upon single and/or dual temperature control unit placement • Volume of space to be controlled [PAGE 42] Controlled Temperature Chamber Mapping and Monitoring • Density of materials storage and potential obstructions • Loaded and empty space air circulation temperature results derived from OQ testing • Mass of materials that enter the Controlled Temperature Chamber vault at higher-than-operating temperatures which add to the heat load of the space. This decreases the ability for the cooling units to bring those products quickly to long-term storage temperature. This issue is inclusive of shipping gels which frequently arrive at location at controlled room temperature and will add significantly to the heat load • Ability of the circulating fans or diffusers to adequately move cooling air • High and low storage locations where warmer air rises • Any independent heat sources in the Controlled Temperature Chamber such as supporting production equipment, where applicable • Open door temperature or storage locations near Controlled Temperature Chamber ingresses and egresses • Frequency of personnel and lift truck ingress/egress operation during working hours • Operations outside working hours • Minimization of nuisance alarms • Air conditioning, or lack thereof, of the Controlled Temperature Chamber loading area where pre-conditioning of the air can limit humidity and consequent frost on evaporator coils • Although there is no formula for the number of sensors in any particular Controlled Temperature Chamber, the distribution must be satisfactory to evaluate the uniformity of temperature within the Controlled Temperature Chamber. The risk areas, doors, airflow, volume load, total volume dimension (size), 3-dimensionality of the space, internal and external heat sources, and obstructions should be taken into account • Sensor(s) should not interfere with normal product movement or storage or be subject to damage from those movements • Sensor(s) should be positioned in multiple geometric planes to accurately convey the temperature of the Controlled Temperature Chamber • The temperature control unit control sensor(s) should be placed in a position such that refrigerated systems respond quickly and effectively to temperature changes in the Controlled Temperature Chamber Data used to determine the number and location of the monitoring sensors may be interpreted in several ways. Two example interpretations are provided in Appendices 2 and 3.
If a variety of containers with commensurate mass are to be stored in the same Controlled Temperature Chamber, then a conservative approach should be taken when designing the probe medium and its own container
It is considered good practice to define the alarm strategy for the Controlled Temperature Chamber. A frequently used approach is provided here as an example:
These are all the alarms generated from the temperature conditioning system and the associated control system. These alarms include system fault, system high or low pressure, high or low temperature, and temperature sensor fault (open or closed circuit). These alarms require an engineering action. Temperature alarm set points are defined on the basis of the system “as commissioned” performance, typically set just outside the three standard deviation range to avoid nuisance alarms, but ensure indication of potential problems as early as possible. Note: if the data from an operational period (at least 24 hours to encompass normal operations) is analyzed then the mean and standard deviation can be calculated. For a normal distribution of data, 99.7% of the results lie within plus or minus three standard deviations of the mean. Therefore, if these set points are used to define normal operating alarms there will be a very small number of false alarms, but only a very small chance that a change in operational performance remains undetected.
These are the alarms from the independent monitoring system, usually configured based on the defined temperature storage limits. [PAGE 44] Controlled Temperature Chamber Mapping and Monitoring For example, a unit with the operational range 2°C to 8°C (36°F to 46°F) may have alarm set points of 3°C and 7°C (37°F and 45°F) as alert limits, with action alarm set points of 2°C and 8°C (36°F and 46°F). Note: this assumes that the calibration accuracy of the sensors is ± 0.5°C, allowing for the permissible rounding error from the specified operational range.
The maintenance history will be checked to ensure that:
Coils have been cleaned, if needed and applicable
Fan operation has been checked
Operation of the unit cooler control valves and thermal expansion valves has been checked
Defrost settings and operation of the defrost system have been verified, if applicable • For standard standalone refrigerators and freezers:
The system envelope will be inspected to ensure that there is no degradation of the materials of construction, door seals, or air leakage paths, as indicated by moisture or ice buildup
The system alarm history (temperature monitoring system, refrigeration system, and general alarms) will be reviewed for the period since the last periodic maintenance to see if there are any negative performance trends indicated, observations will be noted in the maintenance record
The system will be checked to ensure that the refrigeration system set point is being maintained e.g., compressor suction pressure
The maintenance history will be checked to ensure that:
Coils have been cleaned, if needed and applicable
Fan operation has been checked
Operation of the unit cooler control valves and thermal expansion valves has been checked
Defrost settings and operation of the defrost system have been verified, if applicable System performance as commissioned/qualified can be evaluated against the current data from the monitoring system to ensure that the system performance remains unchanged. Controlled Temperature Chambers can be remapped on a periodic basis. For a walk-in unit this is typically done with the unit in use. There may not be an available alternative storage location, with the mapping data evaluated against the original commissioning or qualification mapping data. A risk based approach may be developed to apply varying degrees of rigor depending on the material stored, and the system operating ranges (units operating with a close temperature range can be considered higher risk than those with a wider operating range). [PAGE 48] Controlled Temperature Chamber Mapping and Monitoring Another option is now available: continuous performance verification. The cost of installing and maintaining/calibrating temperature sensors has reduced with the advent of radio transmitters. Similarly, the cost of requalification is a factor to consider. A strategy can be developed utilizing additional sensors to provide reliable confirmation that a system is operating to meet specifications. Three examples of an approach that may be used to provide this assurance are shown in Figures 9.1, 9.2, and 9.3.
[Figure 9.1: Cold Room Layout Example Showing Mapping Sensor Locations and Location of Test Load]
[Figure 9.1 shows a plan of the unit with the sensor locations used for the mapping of the unit. The design is]
symmetrical about a vertical axis, so load testing was carried out by placing a simulated load in the areas shown inside the blue box marked “loaded area”. The load included thermal mass, as the mass of the load may impact the load temperatures in locations adjacent to the outside walls.
[Figure 9.2 shows the locations proposed for a monitoring system to provide continuous verification that the system]
is performing to meet the specifications, to be confirmed from the initial mapping. Note that the impact of reduced performance from a unit cooler or significant degradation of the cold room structure would be detected by the sensors in the locations shown. [PAGE 49] Controlled Temperature Chamber Mapping and Monitoring
[Figure 9.2: Proposed Sensor Locations to Provide Continuous Evidence of System Operation to Meet]
Requirements
[Figure 9.3: Cold Room Layout Example Showing Mapping Sensor Locations and Location of Test Load]
[Figure 9.3 shows a plan of the unit with the sensor locations used for the mapping of the unit. Load testing was]
carried out by placing a simulated load in the areas shown inside the blue box marked “loaded area”. [PAGE 50] Controlled Temperature Chamber Mapping and Monitoring The load did not include thermal mass, as the mass of the load may not impact the temperatures adjacent to the outside walls, but an empty box with external dimensions matching the size of the largest stored volume will be used to provide a “worst case” disruption of airflow.
[Figure 9.4 shows the locations proposed for a monitoring system to provide continuous verification that the system]
is performing to meet the specifications, to be confirmed from the initial mapping. Note that the impact of reduced performance from a unit cooler or significant degradation of the cold room structure would be detected by the sensors in the locations shown.
[Figure 9.4: Proposed Sensor Locations to Provide Continuous Evidence of System Operation to Meet]
Requirements
A point person or department should be formally identified to coordinate the response to temperature excursions outside the specified limits. [PAGE 51] Controlled Temperature Chamber Mapping and Monitoring 10 Operational Issues
The area being mapped should be challenged with specific known operational activities during the thermal mapping process. These activities should simulate normal processes and functions that would occur for routine operations, such as opening interior doors, opening exterior doors (Receiving Dock Doors, Shipping Dock Doors) running of equipment (e.g., thermo-formers, stretch wrappers, forklifts, conveyors) etc. where there is a potential impact to the conditions. By performing these functions and operating equipment during the execution of the mapping studies, cause and effect relationships can be identified for the thermal profile.
An example of a typical operational activity is to examine recovery time for the internal chamber temperature after opening the access door and simulating loading/unloading. It is recommended to determine the time that the chamber door may remain fully open before the monitoring sensors are no longer within the acceptable range. This test can also help to determine how quickly the monitoring sensor recovers and returns to the normal operating temperature range. For an open door recovery test for a new Controlled Temperature Chamber, it is recommended to: • Use a minimum (simulated) load or no load in the storage unit (i.e., no thermal mass stored so the worst case) • Locate temperature sensors as recommended for thermal mapping (with special attention to the sensors located in proximity to the storage locations nearest the door being tested) It is recommended to set the data acquisition rate to 1 minute intervals on the mapping system for this test, because of uncertainty in the time that the test may take. Generally, there are no specific acceptance criteria for this test unless a recovery time is specified in the unit manufacturer’s specifications. It is recommended that the Open Door Recovery Test is performed as an integral part of the mapping study to enable acquisition of the mapping data showing the potential impact of the loading/unloading activities. Note: for larger walk-in Controlled Temperature Chambers fitted with vinyl curtains, the units may be able to maintain the internal conditions (temperatures) indefinitely, as the impact of passing through the curtains is short term and has a negligible impact on the temperature. Vinyl curtains should be well-fitted, rest on the unit walls, and sit just clear of the floor.
interruption) Another type of test that may be helpful from a business continuity, disaster recovery, and operational perspective is a simulated Power Outage Test. This type of test would measure the amount of time the Controlled Temperature Chamber remained within the desired temperature range once electrical power was turned off. Note: although it is expected the Controlled Temperature Chamber will have redundant and backup power supplies, the results from this test would provide data to define how quickly materials need to be moved to another location if the backup power systems failed. Doors to the storage chamber should remain closed during this test. [PAGE 52] Controlled Temperature Chamber Mapping and Monitoring For a power outage/thermal degradation (and subsequent recovery) test for a Controlled Temperature Chamber, it is recommended to: • Use a minimum (simulated) load or with no load in the Controlled Temperature Chamber. This is another test that is recommended as commissioning activity referenced in OQ before the storage unit is put into use, if possible. Proofer question: should this instead be Controlled Temperature Chamber? • Locate temperature sensors as recommended for thermal mapping It is recommended to set the data acquisition rate to 1 minute intervals for this test, because of uncertainty in the time that the test may take. Generally, there are no specific acceptance criteria for this test unless a recovery time is specified in the unit’s manufacturer’s specifications. In addition, once power is restored to the Controlled Temperature Chamber, the amount of time required to have the area return to the appropriate required temperature can be of value for operational considerations for recovery from a disaster, or after a maintenance activity (i.e., elapsed time for recovery of temperature sensor(s) from the time from when power is restored until the last temperature sensor(s) return to acceptable range). Note: this test was previously included in the USP, but has subsequently been removed. Calibration and Calibration Strategies There are benefits to be derived from a considered calibration strategy: • Many of the instruments on the refrigeration system can only be calibrated when the system is emptied for major maintenance: therefore, they are calibrated following the manufactures recommendations • The control sensor can be verified at a single point, as the control functions are usually based on whether the system is above or below the operating set point • The monitoring sensors should be calibrated across the operating range, as they provide the data to support the quality determinations in support of product quality Access Control Areas where product is stored should have a system to prevent unauthorized access. This system can be part of a site keycard system, or use a lock and key with procedural controls which identify who holds, and is entitled to use, the key. Dehumidification Dehumidification should be considered for a cold room or freezer. The life of the equipment can be extended where there are fewer defrost cycles required (reduced expansion/contraction). Dehumidification can also reduce the risk of ice forming on a freezer floor, which presents a safety hazard. For large distribution facilities it may be worth considering the layout, and providing access to a walk-in freezer through a cold room, in order to reduce moisture in the freezer. Equipment Durability When specifying a new facility, it is worthwhile defining the system design life i.e., the expected operating lifespan without significant maintenance. High quality refrigeration systems can have an expected life of 12 to 15 years. Standby systems are usually installed for an installation holding material of a significant commercial value. [PAGE 53] Controlled Temperature Chamber Mapping and Monitoring 11 Packaged Transport Systems
Currently there are two types of Unit Load Devices (ULD) systems suitable for the shipping of temperature sensitive product, designed for use in aircraft. They are powered to either cool or heat the air within the container. A general system description of two systems which are commercially available at the time of publication is provided below for reference.
The Temperature Controlled Cargo Unit (TCCU) is designed for air and ground transport of temperature sensitive pharmaceutical products at 5°C (41°F) (The TCCU is designed to maintain the 5°C (41°F) storage temperature in transport mode for 72 hours when the ambient temperature is 30°C (86°F)). The TCCU is also designed to maintain 5°C (41°F) during brief ambient temperature excursion events ranging from -40°C (-40ºF) to +60°C (+140°F). For air transport, the TCCU is secured to a ULD that meets the requirements of TSO-C90c [23], allowing for use of a fork lift truck for relocating the system, but not a pallet jack. The interior storage space is designed for the foot print of a 40 in × 48 in (102 cm × 122 cm) pallet containing 1100 lb (500 Kg) of product. Interior dimensions of the storage space are 46 in high × 44 in wide × 51.5 in deep (117 cm high × 112 cm wide × 131 cm deep). Access to the storage space is through a hinged door on the front of the TCCU. The exterior dimensions of the TCCU are 58.5 in high × 80.0 in wide × 52.5 in deep (149 cm high × 203 cm wide × 133 cm deep).
Cooling of the storage space is accomplished by fans circulating air over a “cold” plate. When the ambient temperature drops below the storage temperature, the fans circulate air across a “warm” plate. The fans are controlled by electronics that monitor the temperature of the storage space. The electronics includes a status panel to communicate the condition of the TCCU to the End User. A data logger monitors and records the temperature in the storage space. The TCCU includes a Global Positioning System (GPS)/Global System for Mobile (GSM) module that is used to transmit the TCCU’s location, the temperature in the storage area, and the charge status of the cold plate, the warm plate, and the 24 Volts of Direct Current (VDC) battery. The TCCU has two modes of operation: the “recharge mode” and the “transport mode”. In the recharge mode, the TCCU is connected to an Alternating Current (AC) power source between 100-240V, 50 or 60Hz. A refrigeration system cools the cold plate, and a heater in the warm plate recharges the warm plate. The 24V Direct Current (DC) battery is also recharged while the TCCU is connected to AC power. The status panel indicates when the cold plate, the warm plate and the battery have been charged to full capacity. In transport mode, the cargo is loaded into the TCCU and AC power is disconnected. The TCCU is in transport mode any time the AC power is disconnected from the unit. The 24VDC battery supplies power to the fans to circulate air across the “cold” plate or the “warm” plate to maintain 5°C (41°F) in the storage space. The electronic controls and status panel are also powered by the 24VDC battery during transport mode. The control system indicators are described below: • Power indicator: Illuminates when power is applied to the TCCU; when the battery switch/breaker is in the “on” position or when the TCCU is connected to AC power and the AC switch/breaker is in the “on” position [PAGE 54] Controlled Temperature Chamber Mapping and Monitoring • Battery Charge indicator: applicable only in recharge mode; flashes while the battery is charging; continuously on when the battery is charged • Battery Charge Low indicator: turns on for 2 seconds when switching to transport mode; flashes when the battery is low on charge when in transport mode; continuously on when on AC power and battery switch/circuit breaker is off • Warm/Cool Plate Charge indicator: applicable only in recharge mode; flashes while the warm and cool plates are charging; continuously on when both the warm and cool plates are charged • Warm/Cool Plate Low indicator: applicable only in transport mode; turns on for 2 seconds when switching to transport mode; flashes when the TCCU is low on warming or cooling capacity • Warming indicator: illuminates when the warming fans are on • Cooling indicator: illuminates when the cooling fans are on The system is fitted with a data logger, and GSM module, that allows data on the system status, alarm status, and location to be transmitted.
This Temperature Controlled Container is designed for air and ground transport of temperature sensitive pharmaceutical products in the refrigerated or controlled room temperature ranges. The unit is designed to maintain the 5°C (41°F) storage temperature in transport mode for 30 hours when the ambient temperature is between -10°C (14°F) and 30°C (86°F). (Note: the unit is designed to be loaded with product at the storage temperature, it is not intended to warm or cool the load). The unit will also maintain 5°C (41°F) during brief ambient temperature excursion events ranging from -20°C to +40°C (-4°F to -40ºF). The interior storage space is designed for a US 40 in × 48 in (102 cm × 122 cm) or EURO 47.3 in × 31.5 in (120 cm × 80 cm) by pallet containing up to 2100 lb (953 Kg) of product. Interior dimensions of the storage space are 51.7 in high × 51.9 in wide × 52.7 in deep (131 cm high × 132 cm wide × 134 cm deep). Access to the storage space is through a hinged door on the front of the unit. The exterior dimensions are 63.8 in high × 78.7 in wide × 60.4 in deep (162 cm high × 200 cm wide × 153 cm deep).
Cooling of the storage space is accomplished by an air circulation system that passes the air over two electrical heaters and an evaporator, powered by three cooling compressors. The air return temperature is monitored to control the supply air temperature. The control has four incremental steps for cooling, and two for heating. The unit uses two rechargeable Nickel-Metal Hydride (NiMH) batteries for powering the heating and cooling unit of the container. When the heating and cooling unit is not being used, the batteries are only used to power the control unit. When the container is plugged in for charging, the heating and cooling unit uses external power instead of battery power. The control system indicators are: • System on indicator: green Light Emitting Diode (LED) [PAGE 55] Controlled Temperature Chamber Mapping and Monitoring • Charge indicator: blue LED (flashes during charging; fixed when the unit is fully charged) • Alarm indicator: red LED • Alert indicator: yellow LED • Display: showing battery charge level, unit set point and operating temperature/alarm messages Alerts are: • Batteries at 30% charge level • Inside temperature outside specification • Ambient temperature outside specification • Compressor “x” out of order or compressor “x” not starting Alarms are: • Failure of a refrigeration system
There are two possible approaches: • Unit Qualification • Supplier Assessment
It is possible to map each individual unit, to confirm its satisfactory operation and to qualify the service supplier to ensure that their maintenance and calibration quality systems are robust, as this type of equipment is usually provided by a service supplier. The pharmaceutical or biopharmaceutical organization should specify use of the mapped units.
Qualification of the service supplier: the maintenance and calibration quality systems of service suppliers should be reviewed in order to ensure that they are robust The second approach can provide a more flexible system. Usually the pharmaceutical or biopharmaceutical organization will include a temperature logger with the shipment, to provide independent assurance that the specified conditions were maintained during shipping. Regardless of the approach, the method for loading and unloading the unit should be qualified and procedurally defined. Usually the unit arrives on site at temperature, the End User should confirm that the TCCU is visually clean, and load the unit. Loading may take place in CRT or cooled conditions. [PAGE 56] Controlled Temperature Chamber Mapping and Monitoring When the unit is unloaded the shipment should be placed into quarantine until the information from the data logger is checked to confirm that the shipment was within the defined limits for the duration of the shipment. If the shipment was not within the defined limits for the duration of the shipment, a Non-Conformance should be raised and the implications of the out of conditions incident should be investigated.
Temperature controlled over-the-road trailers can be used to move significant amounts of temperature sensitive pharmaceutical product. An approach offered in North America and Europe that takes into account the fact that trucks in most jurisdictions are manufactured to specifications that allow the End Users of these trucks to leverage accepted, voluntary industry standards and focus on the Critical Process Parameters (CPPs) that affect the operational performance of every load carried. Trailers have a different set of environmental and usage profiles when compared to in situ custom-built Controlled Temperature Chambers which are owned and controlled by each pharmaceutical or biopharmaceutical organization e.g.: • Loading and unloading operations • Defrost cycles • Loading patterns Moisture, as a degradation element, is much more prevalent in trailers due to the operational profile i.e., continuous running for a several days, followed by periods of downtime when the trailer is empty. Rigorous inspection of each trailer should be performed prior to loading to account for potential damage by moisture along with potential damage to the sidewalls by forklifts. An approach that takes these differences into account while leveraging the construction standards is presented in this Section of this Guide. These considerations apply to trailers used for long distance transport, as well as those used for local delivery purposes. Distribution of temperature sensitive pharmaceutical or biopharmaceutical product via a temperature controlled trailer is a unit operation that requires Qualification. The mapping of every trailer is not considered a substitute for adopting a defined methodology that identifies suitable equipment and applies a control strategy to the day-to-day operations in order to maintain suitable temperature ranges for pharmaceuticals. Intermodal containers have unique usage patterns, including power interruptions, during loading and unloading operations from the ship. These represent additional considerations to what is presented here and should be included in the qualification of ISO containers. Manufacturers who build temperature controlled vehicles for the food and pharmaceutical/biopharmaceutical industry adhere to voluntary standards that allow the End User to take a “family” approach (i.e., several units of the same make and model) to performance qualification. The focus of activities should be on the key operational and maintenance elements. This can help to establish a high confidence for this distribution unit operation.
Trailers are designed to maintain product temperature. Product loaded into the trailer should be equilibrated to the appropriate temperature before loading. During transit, as heat or cold penetrates the walls, roof, and floor of the trailer, circulating airflows capture the environmental heat or cold. This environmental heat or cold is then conditioned to the desired temperature in the HVAC unit on the front of the trailer. [PAGE 57] Controlled Temperature Chamber Mapping and Monitoring Note: fresh fruits and vegetables produce heat from respiration; this adds load and an allowance for normal degradation of the insulation is a design consideration factored into the sizing of the HVAC unit. Pharmaceutical and biopharmaceutical products do not give off respiration heat; therefore, the HVAC units have additional reserve cooling capacity when the trailers are used for hauling these products. Depending on the geographical area, manufactures build and test trailers to meet the standards of one of two organizations:
In Europe the standards are part of the Agreement on the International Carriage of Perishable Foodstuffs and on the Special Equipment to be Used for such Carriage (ATP) The TMC specifies four general temperature ranges for perishable goods. These ranges coincide with the general storage ranges of many pharmaceutical drug products. The ATP recognizes three temperature ranges. Both the TMC and the ATP evaluate the insulation and HVAC unit in order to certify a unit. In North America, manufacturers can voluntarily certify the capability to one of the performance criteria shown in Table 11.1. Most trailers sold in North America are built to correspond to the F classification. A stamped metal plate providing details of the certification of these trailers should be requested when the order is placed with the trailer manufacturer. Trailer manufactures may issue a plate with the certification post-manufacturing if the vehicle identification number is provided. A quality agreement with the carrier should confirm that the trailer, delivered as new, was either F or DF rated, regardless of the presence or absence of a stamped metal plate. Table 11.1: TMC and ATP Trailer Classification Categories
The trailer floor, roof, walls, and doors are insulated with polyurethane. Polyurethane is a general term used to refer to a family of two part plastics. A blowing agent i.e., CO2 with other gases, provides the foamed characteristic of the material along with a very high insulation value. Over time the blowing agent gas migrates out of the substrate and it is replaced with air and water vapor. This transition occurs slowly over a period of years and is normal. The temperature control unit is sized accordingly to assure a useful life of 15 years with timely maintenance to protect the core insulation of the trailer.
A user requirement for this unit operation is straightforward; the product must be maintained at its designated storage condition and arrive at the destination in acceptable physical condition. Certifying Organization Application TMC North America ATP Europe C65 FRA Controlled Room Temperature C35 FRB Refrigerated F FRC Frozen DF Deep Frozen [PAGE 58] Controlled Temperature Chamber Mapping and Monitoring As the industry standards ensure that there is a minimal trailer-to-trailer difference for each classification as built, the validation approach falls to the firm to consider the impact of loading patterns, inspectional criteria, maintenance, as well as the specification of trailer classification for a matrix approach to assure suitability. The validation exercise is focused on the loading patterns and assuring that proper airflow can be achieved under conditions of heat and cold to maintain the product within acceptable temperature ranges. Even temperature distribution within the trailer is dependent on airflow. Loading practices that block airflow impede the addition or removal of heat and result in product temperature that may not be controlled within the required range. A written protocol should be prepared to document temperatures nearest the product during seasonal extremes. The loading method should be documented. An alternative to actual over-the-road shipments may be the use of thermal chambers in which the loaded trailer can be placed to gather both hot and cold conditions. The validation would utilize a typical trailer type available to the firm. As mentioned above, the F rated trailer is the most common. A successful study on an F rated trailer would also imply that a DF rated trailer would also be suitable because of additional insulation and conditioning capacity. The study should include a demonstration of the effects likely to occur, such as loading practices and defrost cycling that may briefly affect the internal air temperature of the trailer, but will not have an impact on packaged product.
Loading patterns in a well maintained truck are the key determinate in assuring even product temperature within the trailer. The product should be loaded on pallets that allow free airflow the length of the trailer and the product should not be in contact with the walls of the trailer. Double stacking of refrigerated goods should be carefully considered, as airflow distribution in the rear of the trailer may not be sufficient to maintain uniform temperature under extreme conditions.
The Quality Agreement between the carrier and the company should define the shared responsibilities of inspection. The following items should be inspected for each use as they have direct impact on suitability and function of the trailer: • Air distribution chute intact • Air supply, air returns and floor drains clear of debris • Repairs to interior and exterior surfaces • Door seals intact • General cleanliness (visual inspection) [PAGE 59] Controlled Temperature Chamber Mapping and Monitoring 12 Maintenance The supplier of the refrigeration equipment should provide general recommendations for the maintenance of the equipment, in regard to the specific application. These recommendations may not recognize the high value of the stored goods in this application. The potential impact on the maintenance program should be assessed. This Chapter discusses factors which should be considered in a maintenance program. For further information on maintenance programs see the ISPE Good Practice Guide on Maintenance [24].
The coils (unit cooler and air cooled condenser) should be cleaned regularly and checked for any damage to ensure that the performance levels are maintained. Damaged or distorted fins should be straightened with a suitable comb. This inspection should also ensure that there is no corrosion of the fins. Regular inspection should also confirm that the defrost cycle is effective (where applicable), especially if the cycle is adjusted to account for seasonal variation. General Cleaning The approach to cleaning should be considered. Dry cleaning is preferred, in order to minimize risk of contamination. Regular inspection is recommended to ensure that there is no unseen microbial/fungicidal growth. Any growth detected should be addressed.
The condensate pipework should be checked to ensure that it is not damaged and that it has the correct fall and flows freely. Trace heating or insulation also should be checked. Periodic verification during operation is also recommended; this should ensure that the pipe supports are adequate and have not loosened.
There is usually no feedback from the solenoid valve on the unit coolers, so the only way of checking their correct operation is to carry out, periodically, a functional check to verify the performance of each unit cooler.
It is considered a good practice to periodically check the pipe runs, as well as the equipment for leaks, using one of the electronic test devices now available. This may be a mandatory requirement, depending on region. • The system refrigerant fluid level and pressure against the system specification should be periodically checked and documented. Early detection may help avoid system failure • It may be necessary to keep a record of the refrigerant used for the system [PAGE 60] Controlled Temperature Chamber Mapping and Monitoring • Equipment rooms may be fitted with leakage detectors/alarms; these should be calibrated and checked regularly • End Users should be aware of the local regulatory requirements
The panels, doors, door seals, and sealing of utility penetrations can degrade over time (foamed panels may be better in this respect than panels filled with mineral wool). A thermal scan of the installation will allow any degradation to be seen and appropriate action taken. As a minimum, the penetrations should be visually inspected to ensure that they are sound with no leakage/ingress of condensation. For conduit penetrations, the internal sealing also should be checked to ensure that condensation is not leaking inside the conduit.
The entire alarm system should be periodically tested by direct or simulated temperature change against the specified alarm set points and proper functionality of audible and visual alarms at local and/or remote alarm stations (e.g., emails, phone calls, or text based alerts) should be confirmed and documented. Regardless of the root cause, product losses from cold storage-related failures can be prevented with the proper design and operation of the alarm system, and proper End User response to an alarm event. Periodic testing of the alarm system should help to ensure that it will work when needed. The system maintenance procedures can be used to provide a confirmation that the system performance remains satisfactory, supporting a reduced requirement for remapping where appropriate. The data from the monitoring system should be reviewed periodically, to look for any negative performance trends. Suggested maintenance procedures for different system types are suggested. CRT Storage Area (Warehouse)
The system alarm history for the period since the last system maintenance (temperature monitoring system, HVAC system temperature/humidity, and airflow volume sensors as applicable) should be reviewed to see if there are any negative performance trends indicated, observations should be noted in the maintenance record.
The HVAC system should be visually checked to ensure that the system balance remains as commissioned; through verification that balancing dampers remain in their as commissioned/ marked settings.
Heating/cooling coils are checked and cleaned, if necessary.
The control system records should be checked to confirm that control valves are not operating at 100% (indicating that system performance limits are being reached, or that there are utility system issues), unless the control algorithms require that this is what the control valves should do e.g., for dehumidification. [PAGE 61] Controlled Temperature Chamber Mapping and Monitoring Walk-in Refrigerators/Freezers
The system envelope should be inspected to ensure that there is no visible degradation of the materials of construction, door or window seals, door curtains, or air leakage paths, as indicated by moisture or ice buildup.
The system alarm history (temperature monitoring system and refrigeration system general alarms) should be reviewed for the period since the last maintenance to see if there any negative performance trends are indicated; observations should be noted in the maintenance record.
The system should be checked to ensure that the refrigeration system set point is being maintained e.g., compressor suction pressure.
The maintenance history should be checked to ensure that: • Coils have been cleaned, if needed and applicable • Fan operation has been checked • Operation of the unit cooler control valves and thermal expansion valves has been checked • Defrost settings and operation of the defrost system have been verified, if applicable Standalone Refrigerators and Freezers
The system envelope should be inspected to ensure that there is no degradation of the materials of construction, door seals, or air leakage paths, as indicated by moisture or ice buildup.
The system alarm history (temperature monitoring system and refrigeration system general alarms) should be reviewed for the period since the last maintenance to see if there any negative performance trends are indicated; observations should be noted in the maintenance record.
The system should be checked to ensure that the refrigeration system set point is being maintained e.g. compressor suction pressure.
The maintenance history should be checked to ensure that: • Coils have been cleaned, if needed and applicable • Fan operation has been checked • Operation of the unit cooler control valves and thermal expansion valves has been checked • Defrost settings and operation of the defrost system have been verified, if applicable Where a system has multiple monitoring locations e.g., the control sensor, and an independent temperature monitor located to monitor the hot/cold locations in the unit, the preventive maintenance is not required to confirm satisfactory unit operation. The review of current system performance data against the as Qualified data by an SME can be used to confirm consistent system performance. This review should assess the thermal performance of the unit insulation and the conditioning system, allowing a suitably experienced SME to determine if there has been a significant change in performance that may require maintenance activities to improve or if the system is still performing acceptably. [PAGE 62] [PAGE 63] Controlled Temperature Chamber Mapping and Monitoring Appendix 1 Appendix 1 13 Appendix 1 – Example User Requirements Specification
The purpose of this document is to provide the system developer with the user’s requirements for the x°C freezer. Overview Text goes here Background Text goes here Key Objectives The system will store GMP material at x°C to x°C. Main Functions The system shall be capable of storing material at x°C to x°C and provide a general system fault alarm and high and low alarm set points that can interface with the monitoring system. The monitoring system will provide the quality system alarms and provide operator paging. Applicable GMP Requirements and Regulations • 21 CFR Part 11 Compliance (if the system provides an electronic record) • Relevant regulations see Section 1.4 Note: that the specific application may have requirements defined related to the regulations, rather than defining the regulation e.g., “each storage location must have a bar code label defining the location for the inventory management system”.
Ratings of enclosures • Intended operating environment
Utilities:
Power Supply
Electricity: ○ Voltage VAC Hz ○ Amperage ○ Phases ○ Power supply: ˜ Hard wired or cord and plug ˜ Battery backup ˜ Emergency power • Availability:
The (equipment/system) is intended to be operated continuously • Procedural Constraints • Product Contact Materials:
Product in contact with materials • Noise Level Constraints:
The noise made by (any part of) the installation must not exceed 85 dB(A) in operating state, at 1 m (3 ft) from the source • Labeling:
All equipment, control wiring, and instruments shall be labeled and identified • System Life Expectancy • Maintenance:
The system is to be provided with plug and socket connections to facilitate maintenance for internal unit cooler components
Refrigerant pipework is to be provided with isolation valves for major equipment items to facilitate maintenance [PAGE 67] Controlled Temperature Chamber Mapping and Monitoring Appendix 1
User Requirements Specification Sample Walk-in Cold Room System: Storage Requirements Building {x} This document is the property of: Table of Contents General: Purpose and Scope................................................................................................................................ Definitions and Abbreviations............................................................................................................................... References.............................................................................................................................................................. System Description................................................................................................................................................ User Requirements................................................................................................................................................. 5.1 Process Requirements: Capacity...................................................................................................................... 5.2 Process Requirements: Product Physical Properties........................................................................................ 5.3 Process Requirements: System Quality Attributes and System Process Parameters...................................... Automation and Records....................................................................................................................................... Design and Construction: Material Compatibility............................................................................................... Design and Construction: Mechanical................................................................................................................. Design and Construction: Utilities........................................................................................................................ 10 Design and Construction: Electrical..................................................................................................................... 11 Design and Construction: Environmental Health and Safety............................................................................ 12 Design and Construction: Code Compliance – N/A............................................................................................ 13 Operations and Maintenance................................................................................................................................ 14 Miscellaneous – N/A............................................................................................................................................... 15 Change Summary................................................................................................................................................... [PAGE 68] Appendix 1 Controlled Temperature Chamber Mapping and Monitoring General: Purpose and Scope The purpose of this document is to define the user requirements for a walk-in Cold Room to be installed at the XYZ facility. The user requirements stated herein describe what must be achieved for the system to serve its intended purpose. This document is not intended to be prescriptive as to how those user requirements are met. Revise this document to reflect changes that occur throughout the system life cycle and update it to document the current system requirements. Definitions and Abbreviations Term Definition European Conformity (CE) With the CE marking on a product, the manufacturer declares that the product conforms with the essential requirements of the applicable EC directives for environmental, health, and safety. National Electric Code (NEC) Code which sets the standard for electrical systems design and materials of construction. National Electrical Manufacturers Association (NEMA) Association that sets the industry standards in the US for electrical equipment enclosures. Subject Matter Expert (SME) Individuals with specific expertise and responsibility in a particular area or field (e.g., quality unit, engineering, automation, validation, manufacturing, process development). Underwriters Laboratories (UL) A global independent safety science company offering expertise across five key strategic businesses: Product Safety, Environment, Life and Health, Verification and Knowledge Services. Abbreviation Definition BMS Building Management System CE European Conformity dB(A) Unit of measurement for sound intensity, decibels on the “A” scale MCC Motor Control Center OSHA Occupational Safety and Health Administration (US) PI Plant Information RTD Resistance Temperature Detector SCBD System Classification Boundary Diagram SME Subject Matter Expert SOP Standard Operating Procedure UPS Uninterruptible Power Supply URS User Requirements Specification VAC Voltage Alternating Current [PAGE 69] Controlled Temperature Chamber Mapping and Monitoring Appendix 1 References Document Identifier Title System Description The walk-in Cold Room units provide refrigerated storage for XX that support production. This system encompasses the equipment items listed below, as illustrated by referenced P&ID’s: Type Equipment Description P&ID Cold Room (2°C to 8°C) TBA Cold Room TBA The Cold Room will comprise of: • Prefabricated insulated wall panels and roof • Insulated floor slab • Lights, emergency lights, automated door, emergency exit door (actuated by a manual push bar) • Evaporators • Refrigeration skids • Refrigeration piping between refrigeration skids and evaporators • Piping, instruments, controls, and safety features required for operation The Cold Room unit will be controlled locally with the vendor supplied control system, interfacing with operations personnel via the vendor supplied Operator Interface (OIT) and hand switches. It is integrated with the site BMS to allow for performance monitoring, data archiving, and alarming. User Requirements
ID No. Requirement Type Source
for XX. Cold Room interior dimensions must be approximately W × D × 3 H. Note: material will not be stored on the floor; access for cleaning must be provided for all racking. Business Operations
conditions of -2.8°C to 36.7°C (27°F to 98°F). Business ASHRAE/ Operations
room temperature. Business Operations [PAGE 70] Appendix 1 Controlled Temperature Chamber Mapping and Monitoring
ID No. Requirement Type Source
maintain it at temperature. Business Operations
ID No. Requirement Type Source
between 2oC to 8°C (acceptance criteria), with a design performance of 3°C to 7°C (expected results) Quality SME
loaded states Quality SME
Quality SME
Quality SME Automation and Records ID No. Requirement Type Source
dedicated for monitoring cold room temperature (in addition to, and independent from, the unit’s control system). One must measure the localized high temperature zone and one must measure the localized low temperature zone as determined by temperature mapping. Quality SME
calibration e.g., using long cable/radio transmitters. Quality SME
and are dedicated for monitoring must be accurate to within 0.5°C accuracy. Quality SME 6.4 The unit must achieve set point from ambient in 12 hours or less. Business SME
that must control and monitor all aspects of operation, and provide operator interface capability and records of the key aspects of operation. The system must provide redundancy such that either the duty or standby system can operate while the standby system and controls are maintained/repaired. Business SME
in order to issue commands, or change set points/values, or there must be access control to prevent accidental changes to system set points (Note: the refrigeration control system is not required to comply with 21 CFR Part 11 [25] as it provides no records; the independent monitoring system will be compliant). Business SME [PAGE 71] Controlled Temperature Chamber Mapping and Monitoring Appendix 1 ID No. Requirement Type Source
configurable time out where applicable. Business SME
BMS system. Quality SME
manner without loss of configuration or data after power loss and restoration. Business SME
alternating designation to ensure even run time, and provide system redundancy. Business SME
• Fan failure • Door open beyond established time limit • Refrigeration system failure Quality SME
based on their present condition i.e., unacknowledged/ acknowledged etc. Business SME
must complete (i.e., time out) before the alarm becomes active. Business SME
alarm will silence the local annunciation. Business SME
panel) if the system temperature exceeds pre-defined limits, outside the normal operating range. Business SME
if the temperature exceeds normal operating high or low conditions, or the duty system fails. Business SME Design and Construction: Material Compatibility ID No. Requirement Type Source
cleaning and sanitizing chemicals, including bleach and Spor- Klenz® Quality SME
capable of harboring vermin colonies is avoided in detail and construction. All junctions must be sealed with appropriate fillers and mastic beading to prevent insect and rodent ingress to Cold Room construction and materials used in construction and finishing must not be capable of supporting vermin colonies Quality SME [PAGE 72] Appendix 1 Controlled Temperature Chamber Mapping and Monitoring Design and Construction: Mechanical ID No. Requirement Type Source
within 0.25°C (measurement uncertainty) 0.5°C accuracy Business SME
the discharge air stream of each evaporator for troubleshooting (separate to RTDs used for control) Business SME
in line with the insurer’s (Factory Mutual (FM)) requirements Business SME 8.4 The system materials of construction must meet the insurer’s (FM) requirements. Business SME
openings from forklifts and pallet jacks. Business SME
reference by operators using forklifts and pallet jacks. Business SME
dripping on stored material. Quality SME
are open by using a vinyl curtain or other inhibiting device or method. Quality SME
with GMP to facilitate cleaning. Quality SME Design and Construction: Utilities ID No. Requirement Type Source
follows: • Condenser Water – 1.4 bar delta/6°C Utilities must be live to the unit unless it is down for maintenance. Business SME [PAGE 73] Controlled Temperature Chamber Mapping and Monitoring Appendix 1 Design and Construction: Electrical ID No. Requirement Type Source
accordance with National Electrical Code (NEC), Underwriters Laboratories (UL) or European Conformity (CE). Engineering Standard exceptions require XYZ Company approval. Business SME 10.2 Control panels must be labeled per applicable testing organization. Business SME
use at 230VAC, 400VAC, or a combination of both. Electrical power components and equipment must be designed, chosen, and labeled for use on a 50Hz power distribution system. Frequency conversion equipment must not be used to adapt frequency without prior approval. Circuit and plug sizing and types must be determined based on available standard sizes identified in the applicable specification. Business SME
system must be designed for operation with a central UPS system (although it must be connected to generator power, not central UPS power). Business SME
MCCs. Business SME 10.6 Power > 50V must be segregated from power < 50V. EHS SME Design and Construction: Environmental Health and Safety ID No. Requirement Type Source
85dB(A) in operating state, at 1 m (3 ft) from the source (externally and internally). EHS SME
Cold Room in an emergency. EHS SME
activate an external light and initiate a common trouble alarm in an emergency. EHS SME
skids, with connection to the fire alarm (life safety) system. EHS SME Design and Construction: Code Compliance Not Applicable (N/A) [PAGE 74] Appendix 1 Controlled Temperature Chamber Mapping and Monitoring Operations and Maintenance ID No. Requirement Type Source
with required clearances and proper access provided for equipment, components, and instruments. Where necessary, provide access panels or doors as required for replacement or maintenance access. Do not place products requiring regular maintenance at locations that will be inaccessible after construction is completed. Business SME
locations and the maximum quantity of material allowed to be stored. Quality SME
temperature alarms and equipment alarms. Quality SME
to facilitate maintenance. Business SME Miscellaneous Not Applicable (N/A) Change Summary Change Justification [PAGE 75] Controlled Temperature Chamber Mapping and Monitoring Appendix 2 Appendix 2 14 Appendix 2 – Sample Document: Number and Location of Mapping Sensors This sample document defines the number and location of temperature mapping sensors to be used and the Load Test rationale.
This document is intended to provide a record of the rationale used to select the sensor locations for the temperature mapping of the Client’s Warehouse, and the associated Load Test strategy. The mapping will be used to determine the number and location for the permanent monitoring sensors, based on the product storage locations that experience maximum and minimum temperature conditions during simulated normal use. It should be noted that the product stored has no critical humidity requirements; therefore, humidity will be neither mapped nor monitored.
The following points were considered: • External heat gains and losses • Internal heat gains and losses External Heat Gains and Losses The major heat gains and losses to the warehouse are due to the influences of the external environment, with the most significant being through the north wall and ceiling. All other influences will be consistent; areas within the warehouse which are adjacent to the temperature controlled storage room, will be air conditioned. During normal use the doors will be opened for loading and unloading, influencing the internal conditions. Vinyl curtains are placed at each entrance, with inflatable seals to seal onto the truck sides for loading and unloading. Internal Heat Gains and Losses • Lighting: the lighting is from low energy fluorescent lamps; these are left on during the working day • Product: the product stored in the warehouse is supplied at the storage temperature, so will not put a significant heating or cooling load onto the space • Equipment: the equipment used comprises a stacking forklift truck; this is a relatively small intermittent load • Personnel: on average there are approximately two people working in the area – the heat gains are, therefore, small and transient [PAGE 76] Appendix 2 Controlled Temperature Chamber Mapping and Monitoring • Air conditioning is by a single system with outlets equally spaced in the aisles as shown on the attached drawing.6
The areas considered during the mapping are those areas where product will be stored. The sensor locations proposed have been generated using the French Standard “NF X15-140 October 2002 Measurement of air moisture – Climatic and thermostatic chambers – Characterization and verification” [17] for guidance. The chamber has been divided into zones, with each zone supplied by an air conditioning vent. The end zones are different to the center zones in that they have the end wall/door influences. However, the symmetrical nature of the design of the central zones has allowed the number of mapping sensors proposed to be reduced. A temperature sensor should be placed on the lowest and highest product storage points, and at each corner of the room on the racking/product nearest the perimeter. One temperature sensor will be located in the center of these locations at mid-level.
Winter y The design is specified to maintain internal conditions in all conditions up to and including the 95% limits. The initial mapping is to be in summer, the data obtained from this may be used to recommend a reduced number of sensors to be maintained through to the winter season. The mapping will be considered complete when seasonal variation has been experienced that exceeds the 90% design conditions. [PAGE 78] [PAGE 79] Controlled Temperature Chamber Mapping and Monitoring Appendix 3 Appendix 3 15 Appendix 3 – Example Use of Measurement Uncertainty This example describes the use of measurement uncertainty to determine the monitoring sensor locations from the mapping data. For further information on measurement uncertainty see the NSAI – National Metrology Laboratory (NML) [26].7 The maximum temperature and minimum temperature should be found during the mapping activity. This data can be analyzed to determine the locations representing temperature extremes. • Where monitoring sensors can be located at the maximum and minimum temperature spots, alarm limits can be determined based on Critical Operational Data (COD)/Measurement Uncertainty (MU) of sensor and calibration standards • Where monitoring sensors cannot be located at the maximum and minimum temperature spots, an offset should be added to the COD/MU to account for the offset between the maximum and minimum temperature spots and the monitoring sensor(s)
For alarm sensors permanently mounted at a location other than the maximum and minimum temperature locations as determined in mapping, the offset between the maximum and minimum temperature spots and the monitoring sensor(s) should be determined. When establishing upper and lower limits for the alarm range, any offsets due to the sensor location should be included in addition to the COD/MU for each device In addition, the measurement uncertainty of both types of sensors (i.e., the sensors used during temperature mapping and the permanently installed monitoring sensors) should be considered in establishing the alarm limits. Measurement Uncertainty calculation and application: For the low limit: DL ≥ Limit + [GB – Usr] For the high limit: DL ≤ Limit – [GB – Usr] Where: DL = Decision Limit Limit = PAR (Proven Acceptable Range), Action or Safe Operating Limits Guard Band (GB) = k usystem k = coverage factor which must be ≥ 2.00 usystem = calculated measurement uncertainty Usr = Required Uncertainty of Limits (usually = 0 to indicate no allowable excursion from the alarm value) 7 Dubhaltach Mac Lochlainn of the National Standards Authority of Ireland (NSAI) has kindly provided further guidance on the use of measurement uncertainty please see the ISPE website for further information. [PAGE 80] Appendix 3 Controlled Temperature Chamber Mapping and Monitoring Examples Figure 15.1 Given: uT1 = uT2 = uT3 = uT4 = uT5 = uT6 = 0.125°C Usr for each sensor = 0°C (no data available to allow for temperatures above or below the Proven Acceptable Range (PAR)) k = 2 (corresponds to confidence ≥ 97.7% for single sided alarm; 2 σ) PAR = 2°C to 8°C (35.6°F to 46.4°F) GB = us k = 0.125°C * 2 = 0.25°C Example A If all sensors are within GB = 0.25°C of each other, the differences in temperature can be attributed to the measurement uncertainty of the sensors and the location of the monitoring sensor can be at any one of the locations of the mapping sensors. The alarm limits are: DLH = 8 – (GB – Usr) = 7.75°C DLL = 2 + (GB – Usr) = 2.25°C Example B If sensor 1 shows highest temperature at 7.0°C and sensor 4 shows lowest temperature of 6.5°C at that same time, the following applies: a. If you leave the monitoring sensor 5 in the existing location (same as sensor 4), include 0.5°C offset and measurement uncertainty for sensors 1 and 4 in calculation (i) for the high alarm limit. The low alarm limit calculation (ii) remains the same as in Example A: i. DLH = 8 – (0.5 + 2√ (uT1 2 + uT4
Establish rationale for sensor locations. Using the guidance in Section 6 of this Guide, identify sensor locations and document them as follows (this example shows an excessive number of sensors for the space only to demonstrate various rationales): a. Sensors 1 to 9: Basic layout: high and low at each corner plus one in middle of room b. Sensors 10 to 25: high, middle and low on fixed racks due to restriction of air flow and temperature stratification c. Sensor 26: external door to unconditioned space with potential impact on room condition d. Sensors 27, 28, and 29: external wall due to temperature extremes greater than 10oC from room set point e. Sensor 30: potential exposure to heat from defrost cycles of the system f. Sensor 31: monitoring external conditions (for information only; not subject to acceptance criteria) g. Sensor 32: control and/or monitoring sensor location
Define Equipment a. Model – Validator 2000 Data Logger and Sensor Input Modules with T Type Thermocouples b. Description i. Validator 2000 S/N 590030 ii. Sensor Input Modules (SIMs) • 940030 • 940031 • 940032 c. Calibration information i. Validator 2000 last calibration 11/15/2010; calibration due 11/15/2011 ii. Sims last calibration 11/15/2010; calibration due 11/15/2011 iii. Sensor calibration initiated on 12/14/2010 using temperature standard MK 15/65 Kaye 03/14/2010 with temperature reference MKR-80 [PAGE 83] Controlled Temperature Chamber Mapping and Monitoring Appendix 3 • Identify measurement uncertainty of sensors and data collector (from Calibration Report)
Verify that values are being recorded
Start Time: _____
End Time: _____
Evaluate data for temperature uniformity for each sensor a. Minimum reading with time and sensor number b. Maximum reading with time and sensor number c. If minimum and maximum readings are within the Acceptance Criteria for the room, then the uniformity is acceptable for this system d. Compare minimums and maximums to the monitoring device values and determine if relocation of the monitoring sensor is required or an offset in the alarm strategy is required or other action is necessary e. Mean kinetic temperature (for CRT warehouse with areas allowing specified temperature excursions over specified periods of time only) [PAGE 84] [PAGE 85] Controlled Temperature Chamber Mapping and Monitoring Appendix 4 Appendix 4 16 Appendix 4 – Sample Report Recommending the Location for Freezer Note: this is a sample document. The number and location of the sensors should be defined based on the unit; the storage temperatures are based on the product requirements, with the sensors located in thermal fluid as this is the preference of the System Owner who kindly provided this example.
The freezer was mapped using 36 independent sensors connected to a temperature mapping system during commissioning, with the mapping sensors located as shown in Figure 16.1. A series of tests were performed to ensure that the system met performance specifications during simulated use. The freezer performance will be monitored by the BMS, with an independent chart recorder used as a backup system. The mapping data obtained during the commissioning tests was used to determine the BMS and chart recorder sensor locations.
The monitored room air temperatures are intended to be kept between -15°C (5°F) and -25°C (-13°F). The product is placed in the room at temperatures within this range; so it is not considered necessary to separately monitor the product temperature. Temperature monitoring sensors will be located in a small container of glycerin, to simulate the thermal response of the product packaging. Note: in this example the site had data confirming that this was equivalent to the material to be stored in the unit. Monitoring System The BMS and chart recorder sensor elements will be placed in the room and monitor worst case air temperature based on the conclusion contained in this report. There are six temperature sensors for use as freezer temperature monitors. Approach The following test results were used as the basis for determining the BMS and chart recorder sensor locations, so that they represent the worst case conditions (minimum and maximum temperatures) during simulated normal use of the freezer. The sensors are intended to be placed in a location that will see the most rapid changes in the air temperature, in order to achieve the earliest possible alarm in case of an out of limit operation. [PAGE 86] Appendix 4 Controlled Temperature Chamber Mapping and Monitoring
[Figure 16.1: Mapping Sensor Locations]
Commissioning Test 1 – Baseline Readings This test was used to confirm the proper operation of the refrigeration systems by monitoring system operational parameters. The freezer operation was monitored for a minimum of 24 hours, in steady state conditions with no door opening. Commissioning Test 2 – Open Door Test Empty This test was used to determine the effect on the freezer temperature while the freezer sliding door was left open. The test was conducted with the system furthest from the door (Cooling System A) operating, to provide worst case conditions i.e., minimum forced air mixing adjacent to the door). The door was opened for a one-hour period with the internal vinyl curtains closed; the test period was adequate to indicate the conditions that the system would maintain if the door was left open. Commissioning Test 3 – Open Door Test Loaded This test was used to demonstrate the system performance loaded, using empty boxes to simulate the load (maximum volume, minimum thermal mass). The test was conducted with the system furthest from the door (Cooling System A operating, to provide worst case conditions i.e., minimum forced air mixing adjacent to the door). For each load, an open door test was conducted. The door was opened for a one-hour period with the internal vinyl curtains closed; the test period was adequate to indicate the conditions the system would maintain if the door was left open. [PAGE 87] Controlled Temperature Chamber Mapping and Monitoring Appendix 4 Table 16.1: Test Results Considerations The locations recommended for the BMS sensors are those generally representing the minimum and maximum temperatures during the tests, considering the following: • The sensor should ideally be accessible for ease of calibration • The sensor should provide a reading reasonably representative of the minimum and maximum temperatures product will be exposed to during normal operation of the freezer • The highest risks of temperature excursions are during door opening. During operation, normal traffic into the room is performed with the opened door through the curtains of the cold room • The sensors should be distributed, as much as possible, to try to represent the whole freezer • The central area of the freezer is considered to be more stable in terms of temperature than the perimeter zones, as there are no doors and the external environmental influences are significantly less • The accuracy of the mapping sensors used is ± 0.5°C (± 0.9°F) Minimum Temperature Locations The location experiencing the minimum average temperature and minimum temperature during test 1 was location x. The minimum value recorded during testing was x°C/x°F, recorded at sensor x during test 1 and at location x during test 2.
Based on the data the following locations were considered for the BMS sensors. Conclusions The locations selected for the temperature monitoring sensors are: • The locations for the minimum temperature are: • The locations for the maximum temperature are: Note: The following graphs showing the mapping data for each test were attached to the example: • Data from all mapping sensors • Data the sensors selected to provide the monitoring data These showed that the monitoring locations selected provided a reasonable record of the worst case locations (i.e., hottest and coldest). [PAGE 89] Controlled Temperature Chamber Mapping and Monitoring Appendix 5 Appendix 5 17 Appendix 5 – Science and Risk- Based Development and Use of the Risk Assessment The process described in this Appendix uses a risk assessment to determine the risks to system product quality due to the equipment and defines the associated risk controls that must be in place in order to provide an acceptable risk profile for a system.
In order to define the scope, and align it to that of traditional Installation Qualification/Operational Qualification (IQ/ OQ) or combined Installation and Operational Qualification (IOQ), this Guide uses the following assumptions: • The output of the system is considered to be the Product • The inputs to the system are considered to be Qualified i.e., meet specification • The aspects that are reviewed are those within the system boundary • The focus is on product quality (patient safety) • To avoid the assessment becoming a very detailed FMEA, which would not achieve the program goal, the maintenance and calibration quality systems are considered to be in place and effective Information used for the risk assessment includes: • Critical Quality Attributes (CQAs) • Critical Process Parameters (CPPs) • Potential risk to product quality • Source of the risk • Risk controls (design/procedural) • Means of detection of the risk should the controls fail An initial draft risk assessment may be generated by a small number of SMEs in order to make the process more efficient. The information generated should include a system description and control strategy, to ensure that there is a clear definition of the scope of the assessment and a clear understanding of how the system operates. The initial draft risk assessment and supporting information can be reviewed and scored by a larger team of SMEs led by an experienced facilitator, to help to ensure that the operating knowledge and experience of site personnel is captured. The larger team should be composed of the small number of SMEs and additional representatives from quality/validation, operations, and engineering groups/departments. [PAGE 90] Appendix 5 Controlled Temperature Chamber Mapping and Monitoring The following actions are usually predefined: • Low risks are accepted • Medium risks can be accepted by the team, or the team can elect to add additional controls to reduce the risk • High risks should have additional controls added to become medium or low risks (Tables provided in this Section of the Guide show recommended scoring values). The risks are scored using the Tables below based on the design and the planned content of the operational and maintenance procedures. Note: these Tables are examples and are not exclusive. Various high risk assessment gauges and tables are available. Table 17.1: Risk Assessment Chart Rating SEVERITY of the Effect of Failure Likelihood of OCCURRENCE Ability to DETECT the Failure Severe: Serious impact to a critical quality attribute of the output of the system/equipment Impact to final product critical quality attribute Frequent: Failure is almost inevitable Consistent failures observed (e.g., once a week or several times a month) Absolutely uncertain: Existing controls cannot detect the failure No controls are in place Major: Significant impact to a critical quality attribute of the output of the System/equipment Possible impact to final product critical quality attribute Likely: Failure is likely and will occur in most circumstances Repeated failures observed (e.g., once a month or several times a year) Remote: Remote chance that controls will detect the failure A control may be in place but is untested or unreliable Moderate: Possible impact to a critical quality attribute of the output of the system/equipment No impact to final product critical quality attribute Occasional: Failure is probable at some time and has been observed (e.g., once every 1 to 2 years) Moderate: A moderate chance that the control will detect the failure Minor: Minor impact to a critical quality attribute of the output of the system/equipment No impact to final product critical quality attribute Unlikely: Failure could occur at some time Only isolated incidents observed (e.g., once every 3 to 5 years) High: Very likely that the control will detect the failure (e.g., a procedural control) Insignificant: No impact to QA of the output of the system/ equipment No impact to final product critical quality attribute Remote: Failure is extremely unlikely No history of failure Almost certain: The control will detect the failure in almost every instance (e.g., an alarm or automated function) Note: that detection must be accomplished internally to be valid. [PAGE 91] Controlled Temperature Chamber Mapping and Monitoring Appendix 5
Defines where high risks were communicated to senior management for review and acceptance • Conclusions [PAGE 93] Controlled Temperature Chamber Mapping and Monitoring Appendix 6 Appendix 6 18 Appendix 6 – Example Testing Strategies
This Appendix presents an example of developing the mapping strategy for a 20 ft × 20 ft × 10 ft (6 m × 6 m × 3 m) space for storage of up to ten double stacked pallets of materials at a controlled room temperature.
The size of the facility is given as 20 ft × 20 ft × 10 ft (6 m × 6 m × 3 m). In general, the three dimensional space should be divided into at least three planes: • Upper level of space • Middle level of space • Lower level of space
Using the concepts described for spaces up to 70 cubic ft (2 m3), probes should be located on the upper and lower levels at the four corners of the space and a single probe in the center of the box (see Figure 18.1).
[Figure 18.1: Mapping Locations for a CRT Space up to 70 cubic feet (2 cubic meters)]
[Figure 18.2: Mapping Locations for a CRT Space up to 700 cubic feet (20 cubic meters)]
[Figure 18.2 is appropriate as a starting point. Vertical and horizontal distances are not greater than 30 ft (9 m) so]
additional probes are not suggested beyond the probes identified in Figure 18.2. 6. The air supply for the space is a ceiling diffuser with four returns located in each of the corners. There are no racks, shelves, or other obstructions to air flow within the space. The pallets have the potential to be stacked to a height of 6 ft (1.8 m), so will not create significant obstruction to air flow. Material will not be stored near the ceiling along the walls, so there is no concern for “hotspots” in these locations that would not already be detected by the probes mounted at the middle plane along each of the walls. No additional probes would be suggested beyond the probes identified in Figure 18.2. 7. The room is inside a general purpose building that is conditioned throughout the year to 20°C (68°F) so there is no concern for external temperature extremes compared to the controlled environment that could penetrate the walls/ceilings/floors, nor create temperature control issues when the door is opened to move material or people. No additional probes would be suggested (such as near windows, doors, walls, etc.) beyond the probes identified in Figure 18.2. 8. There are lights in the facility; however, there is no product to be stored near the fixtures that might be impacted by heat generated during operation. There are no motors, compressors, computers, or other heat generating equipment located in the space that might impact temperatures in the immediate vicinity. There are no materials being stored in the facility that have the potential for exothermic/endothermic reactions that might impact temperatures in the immediate vicinity. No additional probes would be suggested beyond the probes identified in Figure 18.2. 9. The HVAC system consists of a dedicated single air unit which is a recirculation system with a supply fan, cooling and heating coils. It is located remotely from the space. There is no redundancy which might prescribe the need to test conditions for each unit or during switchover. There are no defrost cycles that would need to be identified and included in the testing cycle, and with no defrost cycles, or significantly colder/hotter temperatures of supply air, there is no need for additional probes to define potential impact on product stored in the immediate [PAGE 95] Controlled Temperature Chamber Mapping and Monitoring Appendix 6 path of supply air. Failure of the air system could have an impact on environmental conditions in the space. This potential impact should be identified and accounted for in the design of the system. Appropriate testing would then be performed to demonstrate capability during Commissioning. For this system, the facility is located inside an environment already controlled to conditions within the limits of the facility; therefore, failure of the air system would not impact the temperature of the space. If there were a potential, the testing strategy would include testing under failure conditions to demonstrate how long the facility can maintain conditions appropriate for storage.
[Figure 18.3: Mapping Locations for a Refrigerator]
A mapping strategy for standard unit refrigerators and walk-in units follows the same development steps as described in Example 1 for a walk-in unit. Due to the potential for air flow blockage from the shelves and/or material stored on the shelves, each level should be considered a mapping zone with a complement of probes assigned to each level. The strategy should consider the unit and potential to relocate intermediate shelves, ideally defining the lower and upper limits, with the test load designed so that shelving may be moved as required during operation. One concept that has been successfully used is to define the limiting parameters for the load on a self-adhesive label attached to the unit door e.g., allow 3in (75 mm) clearance on the side front and rear of the unit, lowest shelf position 4 in (100 mm) from the bottom of the unit, minimum top clearance 4 in (100 mm), maximum room temperature load 20 lb (9 Kg).
[Figure 18.3 shows a typical layout using five probes per shelf. If shelves allow circulation, the intermediate shelf]
probes may be replaced with a probe in the center of the refrigerator. Another option is to place three probes per shelf, alternating corners (front and back) on each level Figure 18.4. An assessment of the potential circulation will dictate the density option, five per shelf for the poorest circulation (solid shelves densely packed), three per shelf for intermediate circulation (wire shelves packed very full), and probes in four corners and middle of refrigerator for good circulation (wire shelves with lots of space for air circulation between contents). [PAGE 96] Appendix 6 Controlled Temperature Chamber Mapping and Monitoring
[Figure 18.4: Alternative Mapping Locations for a Refrigerator]
Temperatures may be monitored in the load or a suitable buffer to record the load temperature rather than the air temperature if there is concern for short temporary fluctuations outside of the acceptable ranges due to defrost cycles, door openings, or other predictable occurrences. The air temperature is affected more by repeatedly opening and closing the door for smaller systems, due to the temperature differences between the internal space and the surrounding environment. The volume of stored material can act as a “heat sink” to maintain the temperature of the space. These loads can be either actual product or simulated product with similar thermal properties. If using simulated product, what is being used and how it is comparable (e.g., 20 ml of water is being used instead of insulin because the thermal properties of water are identical to insulin and will behave in the same manner as insulin stored in this facility and the smallest container stored in the facility is 20 ml) should be documented. The internal air temperature distribution should be mapped in the empty and full state to demonstrate operating capability throughout all states of content. Full state is defined as the maximum amount anticipated being stored in the unit (this should follow manufacturer’s recommendations and be aligned with the requirements in the URS) provided the rationale and control over operational conditions is documented. Afterwards temperature distribution should be checked under conditions of normal use. [PAGE 97] Controlled Temperature Chamber Mapping and Monitoring Appendix 6
The development of a mapping strategy for a warehouse should follow the steps identified above. For example, start with the basic room configuration identified in Figure 18.5. Temperature probes are positioned so that there is not more than 30 ft (9 m) vertical separation or 30 ft (9 m) of horizontal separation.
[Figure 18.5: Mapping Locations for a Warehouse (basic configuration)]
Identify air flow restrictions based on the location of the air supply and location/orientation of full pallet racks, drums, tanks etc. Additional temperature probes should then be added in areas of restricted airflow. In the case of full racks and/or shelves, the restricted air flow may impact the temperature profile so additional probes should be added based on expected air flow pattern.
[Figure 18.6 shows how the locations for additional monitoring probes could be added if the area conditioning air]
supply is from one direction as indicated in the drawings.
[Figure 18.6: Mapping Locations for a Warehouse (where HVAC is from one direction)]
[PAGE 98] Appendix 6 Controlled Temperature Chamber Mapping and Monitoring Mapping of warehouses requires both empty and full state (again, full is defined as the maximum amount anticipated being stored in the facility). In the case of warehouses, the mass of the material is not as significant a factor as the volume, in terms of altering air flow patterns. The full state may be met by simulating the rack loads with empty storage containers (cartons, boxes, pallet boxes, etc.) to obstruct the air flow patterns, as they would when holding actual product. However, if the heating/cooling is provided centrally, the racking nearest the walls may be considered as a layer of insulation; therefore, thermal mass would influence performance. This should be considered when developing the strategy and defining the test strategy. It may be achieved by loading a representative section of racking with a simulated load incorporating thermal mass. Mapping of controlled room temperature warehouses has the same requirements. With this mapping strategy outlined, the probe locations should be reviewed again to verify and document the locations critical to the facility capability.
A warehouse is not typically filled to capacity in the first six months Alternatively, organizations may perform mapping of warehouses over a full year. The external conditions are compared to the specified design conditions, and a judgment made to determine if the results adequately represent all seasons (likely seasonal extremes). These results are used to help define locations for the permanent monitoring locations and to ensure that locations consider the impact of seasonal variations on the locations likely to experience minimum/maximum temperatures. These uses should be taken into consideration during the comparison of the results. For controlled temperature rooms, e.g., cold rooms, it may be considered adequate to map the system once, on the basis that the surrounding environment is controlled and the monitoring system provides adequate assurance that the internal conditions are being maintained, any impact from the outside temperatures on the performance of the heating/cooling system would be visible from the monitoring system, as the temperature profiles in the conditioned space would not be affected. The rationale for the load and seasonal testing should be defined in a document that is reviewed and approved by the Quality Unit and the area/System Owner. A sample document is included in Appendix 2. It is considered good practice to review the initial monitoring data and compare the results with the defined requirements of the URS, to ensure that the requirements have been met. Where user requirements have not been met, the designer/supplier should be asked to review the data and make recommendations for corrective action, to ensure that the system complies with the design specification. Depending on the contracts in place these modifications may be at the design authority’s or equipment supplier’s expense, and should be managed through engineering change management. The USP provides guidance in General Chapter <659> Packaging and Storage Requirements” [11]. [PAGE 100] Appendix 6 Controlled Temperature Chamber Mapping and Monitoring
A. Define the system to be tested and confirm the calibration of the instrumentation to be used. The response time8 for the instrumentation IEST-RP-CC006.3 [27] recommends a 63.2% time constant of no more than 15 seconds for areas with stricter environmental control specifications. This correlates to 75 seconds to achieve 99% (five time constants). This response time should be taken into account when matching temperature sensors with the analytical procedure. The system used should be selected keeping in mind the temperature accuracy required of the facility probes, qualification requirements for the mapping instrumentation, data collection, output and retention capabilities, and compliance with the appropriate electronic record requirements (21 CFR Part 11 [25]/ Eudralex Annex 11 [28]). B. Define the facility operations (static versus dynamic activities to simulate operational states) and control systems (set points, operational parameters) C. Define acceptance criteria/expected results as appropriate D. Probe type and locations Note the strategy defined the rationale for locations E. Define the load test and sequence of loading/unloading F. Define how test issues will be resolved G. Define pre-test requirements (commissioning, calibration, signage, training, etc.) H. Define test steps, mapping under various operational states such as defrost cycles, switch between redundant systems, door openings, people activity, power loss, etc. I. Record test start and stop times J. Record testers K. Provide space for analysis of data with recommendations for actions if required 8 Instrument time response is usually quoted as: “T10-90% or T90-10%. (Referring to rise and fall times respectively) when the instrument is subject to a step change in the input, i.e., the temperature recording system needs to respond faster that conditions are likely to change in order to get an accurate reading – though note that the material stored will have a response time as well – but when testing the goal is to get accurate information to get a complete understanding of how the equipment is performing.” [PAGE 101] Controlled Temperature Chamber Mapping and Monitoring Appendix 7 Appendix 7 19 Appendix 7 – Templates and Attachments
Temperature Chamber
Temperature Range Systems are categorized for the purposes of periodic review considering the system operating temperature range, and the material stored. • Stored Material Type A: for example, API, drug product, stability sample(s), cool/hot packs used to maintain temperature during transportation (if the cool/hot pack temperature is not verified before use) • Stored Material Type B: for example, Work in Progress (WIP), Reference Standards, critical reagents, raw materials • Stored Material Type C: for example, Environmental Monitoring (EM) supplies and reagents, media, test materials Table 19.1: Review Category Based on Material Stored and Temperature Range
The periodic review process must be carried out as follows: • Category 1 Controlled Temperature Chambers: periodic review not to exceed three years from the previous review • Category 2 Controlled Temperature Chambers: periodic review not required; system performance verification must be conducted through a defined maintenance job plan • Category 3 Controlled Temperature Chambers: system performance verification and periodic review is not required There are two methods that may be used to perform the periodic review of the Controlled Temperature Chamber. Stored Material Type Precision Unit: Temperature Range ≤ ± 6°C Standard Unit: Temperature Range
± 6°C Conditioned Room: Controlled Room Temperature* A B C
- as defined in USP [PAGE 102] Appendix 7 Controlled Temperature Chamber Mapping and Monitoring
Is the cooling system still operating with performance aligned with the as commissioned/qualified state? The following is an example of a periodic review for a Controlled Temperature Chamber. The actual review should replace the text given in green as necessary: Example: The results of this review are contained in the report below. There is nothing in the review to indicate that the original mapping results will have changed, the data from the monitoring system still shows that the system is operating within the operating limits, it is therefore considered fit for continued use. [PAGE 103] Controlled Temperature Chamber Mapping and Monitoring Appendix 7 Example Assessment Report with Draft Content9 Reference Aspect Review Conclusion Internal Layout
Locations The racking layout and defined storage locations remain as defined in the commissioning and qualification file per review of the current installation and operations SOP- xxx with the C&Q report RPT-yyyy The locations used to store material remain unchanged, so the effect on the unit airflow and temperature distribution has not changed
The size and or mass of the stored material that was defined in the test strategy or as used for the commissioning and qualification has not changed The size and mass of the material used for the load testing of the Controlled Temperature Chamber remains representative of the material currently stored in the Controlled Temperature Chamber, hence the performance will not have changed Insulation
PM number requires an annual thermal scan of the system verifying the surface temperature remains consistent with the as installed readings, and there are no hot or cold spots, or visual inspection and a review of the cycle time of the refrigeration plant. The thermal scan is consistent with those taken during initial operation confirming that there is no degradation of performance, or a visual inspection and a review of the cycle times show no significant degradation.
Visually inspect the Controlled Temperature Chamber penetrations looking for any leakage or condensation. The Controlled Temperature Chamber was inspected – all utility penetrations are in good repair with no sign of leakage or condensation.
The door, door seals, and vinyl internal curtain were inspected. The door, door seals, and vinyl curtain are in good condition. The vinyl curtain sits on the side of the unit with no air gap and just touches the floor so there is no friction to prevent it closing and no significant air gap. Cooling System
Review alarm history for the refrigeration units and determine if the frequency is normal/ acceptable. The alarm history was reviewed, with a total of 12 engineering alarms, and no quality alarms; all engineering alarms were resolved while keeping the unit inside the operational limits.
Confirm that there is a PM that checks duty standby function, and reviews system operating settings, and that the refrigeration system major components are as installed. The automatic duty standby changeover function is routinely checked, the refrigeration system has not been changed and the system operating parameters: suction and delivery pressure for both systems are within the manufacturer’s tolerances, indicating that the system is operating normally.
The data from the independent monitoring system shows that the system is operating within the operating limits with no indication of a degradation in performance. A review of the system monitoring data shows that the system is still operating within the operating limits with no indication of a degradation in performance.
Confirm system and independent alarms tested. Alarms tested: all function correctly at the defined set points, with the delay periods assigned as noted in the attached sheet. Note: example text is shown in green italic. 9 The draft content should be revised to suit the specific application. [PAGE 104] Appendix 7 Controlled Temperature Chamber Mapping and Monitoring • Revise the template report to reflect the findings for the Controlled Temperature Chamber under review. • Record the results of the review into the Periodic Review Report, recording the location of the information, and attaching copies where appropriate • Define any actions required after review of the information • The report summary must state if the system is considered suitable for ongoing use • If it is concluded that the system is not suitable for ongoing use, a nonconformance shall be utilized to define the actions required, and manage their completion • The Periodic Review Report be reviewed and approved by the System Owner or delegate and Quality Unit
As an alternative to method one, the Controlled Temperature Chamber may be remapped. Remapping should consider the following aspects: • Loading/unloading of the unit • The impact of the load on the unit temperature distribution • The impact of unit defrost on the unit temperature distribution The test plan supporting rationale and mapping acceptance criteria should be approved by the System Owner or delegate and Quality Unit. The results of the mapping shall be used to confirm the number and location of the monitoring probes, or provide the rationale to support modifications to the monitoring system. Record the results of the remapping into the Review Report. The report summary shall define if the system is considered suitable for ongoing use, and shall be approved by the System Owner or delegate, and Quality Unit. If it is concluded that the system is not suitable for ongoing use, a nonconformance shall be utilized to define the actions required, and manage their completion. [PAGE 105] Controlled Temperature Chamber Mapping and Monitoring Appendix 7
JHA Title: Formaldehyde Disinfection of Enclosure Type Equipment JHA Number: Project Name: Site: Project Number: Bldg/Rm#: General Contractor: Contractor Services Prepared By: John Smith Contractor(s): N/A Date: 2/7/2016 Craft(s): Field Service Technician Scheduled Start Date: Reviewed By: Date: Briefly Describe Task: Perform formaldehyde vapor disinfection of Enclosure Type Equipment Required PPE: Lab coat, safety glasses Supplemental PPE: Tyvek suit, full face respirator with formaldehyde cartridges, gloves Required Permits: None Competent Persons(s): John Smith General Comments: Contractor Services workers will set up and perform formaldehyde vapor disinfection of Equipment. Contractor Services will follow procedures outlined in Contractor Services SOP 82 to complete this work. Only Contractor Services personnel will be allowed in the rooms after 5 pm on evening of generation of formaldehyde vapor in the equipment. Disinfection will continue overnight, with neutralization and venting occurring the following morning. Process will generally be completed by 10 am the morning after formaldehyde generation and disinfection. Personal Exposure Level monitors will be set up to detect any formaldehyde leakage from the equipment during the disinfection process. Any leakage detected will be reported on the Decontamination Report. Contractor Services will use short-term monitoring to assure formaldehyde levels in the enclosures have fallen below 0.5 ppm before releasing units back to the client. • Workers shall review the Company Review Comment Record and comply. • Workers shall sign the JHA verifying they have reviewed and will comply with the contents. • A copy of the JHA will be kept at the work area available for review. Work Operation Potential Accidents or Hazards Safe Job Actions Needed
ISPE Concept Paper: Controlled Temperature Chamber Mapping, International Society for Pharmaceutical Engineering (ISPE), Packaging Community of Practice (COP) April 2012, www.ispe.org.
ISPE Good Practice Guide: Cold Chain Management, International Society for Pharmaceutical Engineering (ISPE), First Edition, May 2011, www.ispe.org.
IA-G0046-2 Guide to Good Distribution Practice of Medicinal Products for Human Use, Health Products Regulatory Authority (HPRA) (previously the IMB), 10 April 2014, https://www.hpra.ie/docs/default-source/ publications-forms/guidance-documents/ia-g0046-guide-to-good-distribution-practice-of-medicinal-products-for- human-use-v2.pdf?Status=Master&sfvrsn=8.
IA-G0011-1 Guide to Control and Monitoring of Storage and Transportation Temperature Conditions for Medicinal Products and Active Substances, Health Products Regulatory Authority (HPRA) (previously the IMB), 5 October 2011, https://www.hpra.ie/docs/default-source/publications-forms/guidance-documents/ia-g0011-guide-to-control- and-monitoring-of-storage-and-transportation-conditions-v1.pdf?Status=Master&sfvrsn=16.
Guidelines of 7 March 2013 on Good Distribution Practice of Medicinal Products for Human Use (2013/C 68/01), European Medicines Agency (EMA), Official Journal of the European Union, http://eur-lex.europa.eu/LexUriServ/ LexUriServ.do?uri=OJ:C:2013:068:0001:0014:EN:PDF.
PIC/S Guide: PE 011-1 Good Distribution Practice for Medicinal Products, Pharmaceutical Inspection Convention Pharmaceutical Inspection Co-Operation Scheme (PIC/S), June 2014, www.picscheme.org.
Guidelines of 5 November 2013 on Good Distribution Practice of Medicinal Products for Human Use (Text with EEA relevance) (2013/C 343/01), European Commission, Official Journal of the European Union, http://eur-lex. europa.eu/LexUriServ/LexUriServ.do?uri=OJ:C:2013:343:0001:0014:EN:PDF.
Guidelines for Temperature Control of Drug Products during Storage and Transportation (GUI-0069), Health Canada, 2011, http://www.hc-sc.gc.ca/dhp-mps/alt_formats/pdf/compli-conform/gmp-bpf/docs/GUI-0069-eng.pdf.
WHO Technical Report Series, No. 961 – Forty-fifth Report, Annex 9: Model Guidance for the Storage and Transport of Time- and Temperature-Sensitive Pharmaceutical Products (jointly with the Expert Committee on Biological Standardization), World Health Organization (WHO) Expert Committee on Specifications for Pharmaceutical Preparations, 2011, http://apps.who.int/medicinedocs/documents/s18652en/s18652en.pdf.
AL Alternating Current API Active Pharmaceutical Ingredient ASHRAE American Society of Heating, Refrigerating and Air-Conditioning Engineers ATP Agreement on the International Carriage of Perishable Foodstuffs and on the Special Equipment to be Used for such Carriage (EU) BAS Building Automation System BMS Building Management System CRT Controlled Room Temperature COD Critical Operational Data CPP Critical Process Parameter CQA Critical Quality Attribute DC Direct Current EHS Environment, Health, and Safety FAT Factory Acceptance Test FMEA Failure Mode Effects Analysis GDP Good Distribution Practice GSM Global System for Mobile HMI Human Machine Interface HVAC I/O Input/Output IQ Installation Qualification OQ Operational Qualification MCC Motor Control Center MU Measurement Uncertainty OQ Operational Qualification [PAGE 112] Appendix 9 Controlled Temperature Chamber Mapping and Monitoring P&ID Piping and Instrumentation Diagram RH Relative Humidity RTD Resistance Temperature Detector SME Subject Matter Expert SOP Standard Operating Procedure TCCU Temperature Controlled Cargo Unit TMC Technology & Maintenance Council (US) ULD Unit Load Devices UPS Uninterruptible Power Supply URS User Requirements Specification USP United States Pharmacopeia VDC Volts of Direct Current WIP Work in Progress
Building Management System (BMS) A computerized system that controls, monitors, and optimizes building services, this may include environmental conditions, heating and cooling systems, elevator systems, lighting, and security. Cold Any temperature not exceeding 8°C (46°F) is cold. A refrigerator is a cold place in which the temperature is maintained thermostatically between 2° and 8°C (36° and 46°F). Cool Any temperature between 8° and 15°C (46° and 59°F) is cool. An article for which storage in a cool place is directed may, alternatively, be stored and distributed in a refrigerator, unless otherwise specified by the individual monograph. Commissioning A well planned, documented, and managed engineering approach to the start-up and turnover of facilities, systems, and equipment to the end-user, that results in a safe and functional environment that meets established design requirements and stakeholder expectations [PAGE 113] Controlled Temperature Chamber Mapping and Monitoring Appendix 9 Controlled Cold Temperature (CCT) Temperature maintained thermostatically between 2° and 8°C (36° and 46°F), that allows for excursions in temperature between 0° and 15°C (32° and 59°F) that may be experienced during storage, shipping, and distribution such that the allowable calculated mean kinetic temperature is not more than 8°C (46°F). Controlled Room Temperature (CRT) Temperature maintained thermostatically that encompasses the usual and customary working environment of 20° to 25°C (68° to 77°F); that results in a mean kinetic temperature calculated to be not more than 25°C; and that allows for excursions between 15° and 30°C (59° and 86°F) that are experienced in pharmacies, hospitals, and warehouses. Dry Place A place that does not exceed 40% average relative humidity at Controlled Room Temperature or the equivalent water vapor pressure at other temperatures. Engineering Change Management (ECM) (ASTM E2500) Prior to system or facility acceptance, changes managed by an approved through SMEs. Changes affecting Critical Aspects should be communicated to the Quality Unit. Excessive Heat Any temperature above 40°C (104°F). Equipment Qualification Confirming that there is adequate documentation to confirm that equipment is installed and operates according to its specifications, and is fit for its intended use. Freezer A place in which the temperature is maintained thermostatically between -25° and -10°C (-13° and 14°F). Note: the freezing point is defined as the temperature at which a liquid substance turns to a solid. The term frozen is applied to the solid product. Good Engineering Practice (GEP) A system whereby individual design decisions are performed by qualified personnel and documented so that they can be traced from user requirements through final design. GEP documentation considers purpose, responsible party, references, assumptions, calculation method, conclusions, and impact upon other facets of design. GEPs take industry practices, constructability, economics, regulatory requirements, and safety into account. Mean Kinetic Temperature (MKT) The single calculated temperature at which the total amount of degradation over a particular period is equal to the sum of the individual degradations that would occur at various temperatures. [PAGE 114] Appendix 9 Controlled Temperature Chamber Mapping and Monitoring Periodic Review A documented assessment of documentation, procedures, records, and performance to ensure that facilities, equipment, and systems continue to be fit for purpose and safety regulatory compliance requirements. The frequency of periodic review is dependent upon the complexity, criticality, and rate of change. Protection from Freezing Where, in addition to the risk of breakage of the container, freezing subjects an article to loss of strength or potency or to destructive alteration of its characteristics, the container label bears an appropriate instruction to protect the article from freezing. Qualification (FDA) Activities undertaken to demonstrate that utilities and equipment are suitable for their intended use and perform properly. Quality Unit (QU) The Quality Unit has a key role within the quality management system governing facilities, systems, and equipment. In addition to acting as a Subject Matter Expert (SME), the Quality Unit is responsible for overseeing quality and compliance. Sensor (FDA) A peripheral input device which senses some variable in the system environment, such as temperature, and converts it to an electrical signal which can be further converted to a digital signal for processing by the computer. Publication Source: FDA Glossary of Computerized System and Software Development Technology. Warm Any temperature between 30° and 40°C (86° and 104°F). [PAGE 115] [PAGE 116] 600 N. West Shore Blvd., Suite 900, Tampa, Florida 33609 USA Tel: +1-813-960-2105, Fax: +1-813-264-2816 www.ISPE.org